2017-09-28 09:38:49 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17081385 |
| W. P. B. PERMIT: 16041215 |
| ADD: 2001 S. DIXIE HWY. |
| CONT: MAC ENTERPRISES |
| TEL: 561-236-3627 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. SEPT. 28/ 2017 |
| ACTION: DENIED |
| |
| 1) COMPLIED. TEW & TAYLOR WILL NOT BE PROVIDING |
| INSPECTION SERVICES FOR THIS PERMIT. |
| |
| 2) 2ND REQUEST. COMMENT NEVER ADDRESSED BY THE |
| STRUCTURAL ENGINEERS. |
| 1ST ROUND OF COMMENTS. THIS REVISION 17081385 |
| REFERENCED PERMIT 16041215 AS THE PRIME PERMIT. PLEASE |
| NOTE UNDER THE PRIME PERMIT THE STRUCTURAL ENGINEERING |
| COMPANY FOR THE PROJECT WAS BCC ENGINEERING WITH |
| CHRISTIAN AQUINO THE STRUCTURAL P. E. THE SUBMITTED |
| PLANS WAS CREATED BY EDGER DUENAS P. E. WITH BUNKER |
| ENGINEERING. IS EDGER DUENAS P. E. EITHER A DELEGATE |
| ENGINEER OR A SUCCESSOR ENGINEER? |
| |
| 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| 61G-15-30.006 (3). DELEGATED ENGINEER |
| 61G 15-27.001 SUCCESSOR PROFESSIONAL ENGINEERING. |
| |
| 3) 2ND REQUEST. COMMENT NEVER ADDRESSED BY THE |
| STRUCTURAL ENGINEERS. |
| 1ST ROUND OF COMMENTS. DISCREPANCY IN PLANS, THE |
| ORIGINAL PERMIT 16041215 WAS DESIGNED TO 180 MPH, |
| BUILDING CATEGORY III AND EXPOSURE C. SINCE THEN THERE |
| HAS BEEN MEETINGS FOR EXPANDING THE SCHOOL, AND A |
| FOUNDATION PERMIT APPLIED FOR. THIS NEW SECTION OR WING |
| IS AN ADDITION TO THE ORIGINAL BUILDING AND THE |
| OCCUPANT LOAD WILL QUALIFY THIS BUILDING TO BE A |
| THRESHOLD BUILDING. THE ORIGINAL DESIGN WAS IN SINK FOR |
| THE ADDITION WITH THE CLASSIFICATION AND BUILDING |
| CLASSIFICATION. THE NEW BUILDING DESIGN SHOWS A WIND |
| SPEED AT 170 VULT AND A EXPOSURE B. DISCREPANCY IN |
| PLANS. 107.2.1.3. |
| |
| PLEASE REVIEW 2014 FBC-B 609.4.2 SURFACE ROUGHNESS |
| CATEGORIES. SURFACE ROUGHNESS C. THIS SURFACE ROUGHNESS |
| SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| 100 FEET (30 M) HORIZONTALLY IN ANY DIRECTION OF OPEN |
| AREAS OF SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT |
| EXTENDS MORE THAN 600 FEET IN THE UPWIND DIRECTION AND |
| A WIDTH GREATER THAN 150 FEET. |
| |
| FBC-B TABLE 1604.5. RISK CATEGORY OF BUILDINGS AND |
| OTHER STRUCTURES. RISK CATEGORY III. BUILDINGS AND |
| OTHER STRUCTURES CONTAINING ELEMENTARY SCHOOL, |
| SECONDARY SCHOOL OR DAY CARE FACILITIES WITH AN |
| OCCUPANT LOAD GREATER THAN 250. |
| |
| 4) BUILDING PROVISO: THE APPLICANT WILL NEED TO SUBMIT |
| FOR EITHER A LOCAL PRODUCT APPROVAL OR A SITE SPECIFIC |
| PRODUCT APPROVAL, AND WILL NEED TO FILE OUT THE FORMS |
| AND FOLLOW THE PROCEDURES TO OBTAIN A LOCAL/ SITE |
| SPECIFIC PRODUCT APPROVAL. |
| 1ST ROUND OF COMMENTS. SHEET A.1 SHOWS 3 DOORS AS |
| EXISTING OVERHEAD DOORS, 122,123 & 124. PLEASE NOTE |
| THAT PREVIOUS REVISION THESE OPENINGS WERE REVISED TO |
| BE MODIFIED. UNDER REVISION 17070951 THE HEADERS WERE |
| EXPANDED, AND UNDER REVISION 16080972 WAS APPLIED FOR |
| OVERHEAD GARAGE DOORS WITH HYDRAULIC LIFTS. THIS |
| REVISION WAS DENIED ONCE BUT HAS NEVER REAPPLIED IT IS |
| AN OPEN REVISION THAT HAS TO BE RESOLVED BEFORE A |
| CERTIFICATE OF OCCUPANCY CAN BE ISSUED. |
| |
| 5) COMPLIED. |
| |
| 6) 2ND REQUEST. COMMENT NEVER ADDRESSED BY THE |
| STRUCTURAL ENGINEERS. |
| 1ST ROUND OF COMMENTS. STRUCTURAL SHEET 1OF 1 INDICATES |
| A W 14X26 STEEL BEAM AND 2 VERTICAL 4X4 LEGS. THE PLANS |
| DO NOT INDICATE THE WELDS TO THE TOP OF THE VERTICAL |
| LEG NOR THE BOTTOM WELDS. THE OTHER ISSUE IS THE A/C |
| STAND BY OTHERS. THE VERTICAL LEGS APPEAR TO STOP AT |
| THE ROOF LINE. THE PLANS INDICATE THE ROOF STAND BY |
| OTHERS, THIS MEANS THE ROOF STAND MUST HAVE THEIR |
| SUPPORT LEGS AT 33 INCHES APART. THIS ALSO MEANS THE |
| OTHER LEGS OF THE A/C STAND WILL HAVE TO HIT THE OTHER |
| SUPPORTS PERFECTLY, NO MENTION OF HOW THE ROOF STANDS |
| ARE TO BE ANCHORED? 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED . |
| |
| 7) 2ND REQUEST. COMMENT NEVER ADDRESSED BY THE |
| STRUCTURAL ENGINEERS. |
| 1ST ROUND OF COMMENTS. SHEET A1 INDICATES WITH NOTE 11 |
| A HOOD SYSTEM. THIS WILL REQUIRE A SEPARATE PERMIT AND |
| ROOF BRACING AND FRAMING FOR THE NEW ROOF TOP OPENING |
| AND ANCHORING FOR THE ROOF TOP CURBS AND INTAKE AND |
| EXHAUST SYSTEMS. FOR ALL ROOF TOP EQUIPMENT, CURBS, |
| FANS OR A/C STANDS, DETAILED ATTACHMENT TO THE ROOF |
| FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND |
| TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |