Plan Review Notes
Plan Review Notes For Permit 17081385
Permit Number 17081385
Review Stop P
Sequence Number 1
Notes
Date Text
2017-09-13 10:39:581) SHT. A.1 SHOWS 2 COLD WELLS AND ONE HOT WELL BUT THE
 HOT WELL IS NOT SHOWN ON THE PLUMBING PLAN ON SHT. P.1
 OR ON THE WATER RISER. CLARIFY.
 2) IF THE HOT AND COLD WELLS ARE PART OF A SERVING LINE
 THEN COMPLIANCE WITH 2014 FBC-ACCESS. SEC.904.5 MAY BE
 REQUIRED. CLARIFY.
 3) SHT.P.1 SHOWS A STEAMER DISCHARGING TO THE GREASY
 WASTE SYSTEM. THE MAXIMUM TEMPERATURE OF ANY DISCHARGE
 TO A DRAINAGE SYSTEM SHALL NOT EXCEED 140 DEGREES. 2014
 FBC-PLUMBING SEC.803.1. THIS SHALL ALSO APPLY TO THE
 DISHWASHING EQUIPMENT AND THE HOT WELL. CLARIFY.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 5) IF THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE
 SOURCE OF HOT WATER TO THE FIXTURE(S) THAT REQUIRE HOT
 WATER EXCEEDS 50 FEET THEN A HOT WATER RECIRCULATING
 LINE SHALL BE REQUIRED PER 2014 FBC PLUMBING SEC.
 607.2. THE RECIRCULATING LINE SHALL BE INSULATED IN
 ACCORDANCE WITH THE 2014 FBC-ENERGY SEC. C404.5.
 6) SHT. P.2 - THE GREASE LINE RISER SHOWS AN EXISTING
 50 GALLON GREASE INTERCEPTOR. THE EXISTING PLANS ON
 FILE WITH THE CITY FOR THIS STRUCTURE SHOW 2 SCHIER 75
 GPM GREASE INTERCEPTORS. REVISE THE PLANS TO SHOW THE
 CORRECT INTERCEPTORS. REFER TO EXISTING PERMIT NUMBER
 16041215.
 7) SUBMIT CALCULATIONS FOR THE ESTIMATED GREASEY WASTE
 FLOW INTO THE EXISTING INTERCEPTORS. COMPLY WITH 2014
 FBC-PLUMBING SEC.1003.2, 1003.3.4.
 8) SHT. P.1 SHOWS TWO COLD WELLS BUT THE SANITARY RISER
 ON SHT. P.2 ONLY SHOWS ONE. THIS ALSO OCCURS ON THE
 WATER RISER. CLARIFY.
 9) SUBMIT DETAILS FOR THERMAL EXPANSION CONTROL FOR THE
 HOT WATER SYSTEM PER 2014 FBC-PLUMBING SEC.607.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW