Plan Review Notes
Plan Review Notes For Permit 17081385
Permit Number 17081385
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-05 10:41:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081385
 9/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL OR HVAC PLAN SHEETS WERE INCLUDED IN
 THE SET. THE ORIGINAL HVAC PLANS SUBMITTED UNDER THE
 MASTER PERMT #16041215 SHOW AHU- 10 & 11 FUNCTIONING IN
 THE AREA OF THE NEW KITCHEN. PLEASE NOTE THAT THESE
 SYSTEMS WERE SIZED AND DESIGNED TO CONDITION THE
 REMOVED OFFICES AND MAY HAVE TO BE ALTERED TO
 ACCOMODATE THE NEW KITCHEN. PLEASE PROVIDE UPDATED
 PLANS, AND
  
 NOTE THAT AIR SUPPLIED OR EXHAUSTED FROM A KITCHEN
 SHALL NOT BE RECIRCULATED TO OTHER ROOMS OR SPACES
 OUTSIDE OF THE KITCHEN- TABLLE 403.3 FOOTNOTE B.
  
 2) PROVIDE AN AIR BALANCE CALCULATION- SECTION 501.5.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW
 GAS-FIRED COOKING APPLIANCES- SEE SECTION 304 FBC-14
 FUEL GAS.
  
 4) SUBMIT PRODUCT DATA SHEETS FOR THE NEW COOKING
 APPLIANCES- SECTION 623.1 FBC-14 FUEL GAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  