Plan Review Notes For Permit 17081385 |
Permit Number |
17081385 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-05 10:41:23 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17081385 | | 9/5/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) NO MECHANICAL OR HVAC PLAN SHEETS WERE INCLUDED IN | | THE SET. THE ORIGINAL HVAC PLANS SUBMITTED UNDER THE | | MASTER PERMT #16041215 SHOW AHU- 10 & 11 FUNCTIONING IN | | THE AREA OF THE NEW KITCHEN. PLEASE NOTE THAT THESE | | SYSTEMS WERE SIZED AND DESIGNED TO CONDITION THE | | REMOVED OFFICES AND MAY HAVE TO BE ALTERED TO | | ACCOMODATE THE NEW KITCHEN. PLEASE PROVIDE UPDATED | | PLANS, AND | | | | NOTE THAT AIR SUPPLIED OR EXHAUSTED FROM A KITCHEN | | SHALL NOT BE RECIRCULATED TO OTHER ROOMS OR SPACES | | OUTSIDE OF THE KITCHEN- TABLLE 403.3 FOOTNOTE B. | | | | 2) PROVIDE AN AIR BALANCE CALCULATION- SECTION 501.5. | | | | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW | | GAS-FIRED COOKING APPLIANCES- SEE SECTION 304 FBC-14 | | FUEL GAS. | | | | 4) SUBMIT PRODUCT DATA SHEETS FOR THE NEW COOKING | | APPLIANCES- SECTION 623.1 FBC-14 FUEL GAS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|