Plan Review Notes
Plan Review Notes For Permit 17081385
Permit Number 17081385
Review Stop B
Sequence Number 1
Notes
Date Text
2017-09-05 15:12:00BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081385
 W. P. B. PERMIT: 16041215
 ADD: 2001 S. DIXIE HWY.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 06/ 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION. THIS PROJECT
 HAS HAD BOTH PLAN REVIEW AND INSPECTIONS COMPLETED BY
 TEW & TAYLOR A PRIVATE PROVIDER COMPANY. A CONDITIONAL
 USE CERTIFICATE OF COMPLIANCE WAS ISSUED BY TEW &
 TAYLOR SINCE THERE HAS BEEN NO CERTIFICATE OF
 OCCUPANCY, HAS NOT BEEN ISSUED THEN SHOULDN?T TEW &
 TAYLOR CONTINUE TO PROVIDE SERVICES? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THIS REVISION 17081385 REFERENCED PERMIT 16041215 AS
 THE PRIME PERMIT. PLEASE NOTE UNDER THE PRIME PERMIT
 THE STRUCTURAL ENGINEERING COMPANY FOR THE PROJECT WAS
 BCC ENGINEERING WITH CHRISTIAN AQUINO THE STRUCTURAL P.
 E. THE SUBMITTED PLANS WAS CREATED BY EDGER DUENAS P.
 E. WITH BUNKER ENGINEERING. IS EDGER DUENAS P. E.
 EITHER A DELEGATE ENGINEER OR A SUCCESSOR ENGINEER?
  
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3). DELEGATED ENGINEER
 61G 15-27.001 SUCCESSOR PROFESSIONAL ENGINEERING.
  
 3) DISCREPANCY IN PLANS, THE ORIGINAL PERMIT 16041215
 WAS DESIGNED TO 180 MPH, BUILDING CATEGORY III AND
 EXPOSURE C. SINCE THEN THERE HAS BEEN MEETINGS FOR
 EXPANDING THE SCHOOL, AND A FOUNDATION PERMIT APPLIED
 FOR. THIS NEW SECTION OR WING IS AN ADDITION TO THE
 ORIGINAL BUILDING AND THE OCCUPANT LOAD WILL QUALIFY
 THIS BUILDING TO BE A THRESHOLD BUILDING. THE ORIGINAL
 DESIGN WAS IN SINK FOR THE ADDITION WITH THE
 CLASSIFICATION AND BUILDING CLASSIFICATION. THE NEW
 BUILDING DESIGN SHOWS A WIND SPEED AT 170 VULT AND A
 EXPOSURE B. DISCREPANCY IN PLANS. 107.2.1.3.
  
 PLEASE REVIEW 2014 FBC-B 609.4.2 SURFACE ROUGHNESS
 CATEGORIES. SURFACE ROUGHNESS C. THIS SURFACE ROUGHNESS
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE
 ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET (30 M) HORIZONTALLY IN ANY DIRECTION OF OPEN
 AREAS OF SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT
 EXTENDS MORE THAN 600 FEET IN THE UPWIND DIRECTION AND
 A WIDTH GREATER THAN 150 FEET.
  
 FBC-B TABLE 1604.5. RISK CATEGORY OF BUILDINGS AND
 OTHER STRUCTURES. RISK CATEGORY III. BUILDINGS AND
 OTHER STRUCTURES CONTAINING ELEMENTARY SCHOOL,
 SECONDARY SCHOOL OR DAY CARE FACILITIES WITH AN
 OCCUPANT LOAD GREATER THAN 250.
  
 4) SHEET A.1 SHOWS 3 DOORS AS EXISTING OVERHEAD DOORS,
 122,123 & 124. PLEASE NOTE THAT PREVIOUS REVISION THESE
 OPENINGS WERE REVISED TO BE MODIFIED. UNDER REVISION
 17070951 THE HEADERS WERE EXPANDED, AND UNDER REVISION
 16080972 WAS APPLIED FOR OVERHEAD GARAGE DOORS WITH
 HYDRAULIC LIFTS. THIS REVISION WAS DENIED ONCE BUT HAS
 NEVER REAPPLIED IT IS AN OPEN REVISION THAT HAS TO BE
 RESOLVED BEFORE A CERTIFICATE OF OCCUPANCY CAN BE
 ISSUED.
  
 5) SHEET A1 SHOWS UNITS LABELED 19 & 20 A COLD WELL AND
 A HOT WELL, IS THIS PART OF A SERVING LINE? IS
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 904.5 FOOD
 SERVICE LINES REQUIRED.
  
 5A) 904.5.1 SELF-SERVICE SHELVES AND DISPENSING
 DEVICES. SELF-SERVICE SHELVES AND DISPENSING DEVICES
 FOR TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
  
 5B) 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL
 BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 6) STRUCTURAL SHEET 1OF 1 INDICATES A W 14X26 STEEL
 BEAM AND 2 VERTICAL 4X4 LEGS. THE PLANS DO NOT INDICATE
 THE WELDS TO THE TOP OF THE VERTICAL LEG NOR THE BOTTOM
 WELDS. THE OTHER ISSUE IS THE A/C STAND BY OTHERS. THE
 VERTICAL LEGS APPEAR TO STOP AT THE ROOF LINE. THE
 PLANS INDICATE THE ROOF STAND BY OTHERS, THIS MEANS THE
 ROOF STAND MUST HAVE THEIR SUPPORT LEGS AT 33 INCHES
 APART. THIS ALSO MEANS THE OTHER LEGS OF THE A/C STAND
 WILL HAVE TO HIT THE OTHER SUPPORTS PERFECTLY, NO
 MENTION OF HOW THE ROOF STANDS ARE TO BE ANCHORED?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED .
  
 7) SHEET A1 INDICATES WITH NOTE 11 A HOOD SYSTEM. THIS
 WILL REQUIRE A SEPARATE PERMIT AND ROOF BRACING AND
 FRAMING FOR THE NEW ROOF TOP OPENING AND ANCHORING FOR
 THE ROOF TOP CURBS AND INTAKE AND EXHAUST SYSTEMS. FOR
 ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  