2017-08-30 14:01:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF MULTIPLE FLEXHEAD PIPING
 ATTACHING TO THE EXISTING SYSTEM. THE EXISTING SYSTEM
 WAS NOT DESIGNED WITH FLEXHEAD PIPING.
  
 DUE TO THE POTENTIAL FOR ADDED FRICTION LOSS OF THIS
 PIPING PLEASE PROVIDE THE APPLICABLE NEW HYDRALIC
 CALCULATIONS FOR THIS EXISTING SYSTEM WITH THE ADDED
 FLEXHEAD PIPING TO SHOW THE REQUIRED FLOW.
  
  
  
 2) MANUFACTURES SPECIFICATION SHEETS FOR THE FLEXHEAD
 PIPING WAS NOT PROVIDED.
  
 PLEASE PROVIDE THE APPLICABLE SPEC SHEETS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  