Plan Review Notes For Permit 17081371 |
Permit Number |
17081371 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-30 14:01:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF MULTIPLE FLEXHEAD PIPING | | ATTACHING TO THE EXISTING SYSTEM. THE EXISTING SYSTEM | | WAS NOT DESIGNED WITH FLEXHEAD PIPING. | | | | DUE TO THE POTENTIAL FOR ADDED FRICTION LOSS OF THIS | | PIPING PLEASE PROVIDE THE APPLICABLE NEW HYDRALIC | | CALCULATIONS FOR THIS EXISTING SYSTEM WITH THE ADDED | | FLEXHEAD PIPING TO SHOW THE REQUIRED FLOW. | | | | | | | | 2) MANUFACTURES SPECIFICATION SHEETS FOR THE FLEXHEAD | | PIPING WAS NOT PROVIDED. | | | | PLEASE PROVIDE THE APPLICABLE SPEC SHEETS. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|