Plan Review Notes
Plan Review Notes For Permit 17081337
Permit Number 17081337
Review Stop B
Sequence Number 2
Notes
Date Text
2018-01-05 17:20:27REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE BASE FLOOD ELEVATION (BFE) IS 7' NGVD
 '29. THE PERMIT APPLICATION DATE IS AUGUST 29, 2017.
 THE CITY OF WEST PALM BEACH FLOOD ORDINANCE THAT WAS IN
 EFFECT AT THAT TIME HAS A 1 FOOT FREEBOARD THAT
 REQUIRES THE FINISH FLOOR AND EQUIPMENT TO BE A MINIMUM
 OF ONE FOOT (1') ABOVE THE BFE. THE PLANS SPECIFY A
 FINISH FLOOR ELEVATION OF 8' NGVD WHICH COMPLIES WITH
 THE FLOOD ORDINANCE IN EFFECT AT THE TIME OF
 APPLICATION. NOTE: ELEVATION CERTIFICATES WILL BE
 REQUIRED TO BE SUBMITTED DURING AND AFTER CONSTRUCTION.
  
 2) WALL SECTIONS B AND C ON SHEET A.07 DO NOT MATCH THE
 STRUCTURAL PLANS FOR THE LOGGIA COLUMNS AND BEAMS. THE
 ARCHITECTURAL PLANS SHOW WOOD WRAPPED METAL COLUMNS AND
 PSL WOOD BEAMS. THE STRUCTURAL DRAWINGS HAVE REINFORCED
 MASONRY COLUMNS AND CONCRETE BEAMS. PLEASE COORDINATE
 THE DRAWINGS. FBC107.2.1
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. ALL OF THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. ALL OF THE NOA OR FL
 NUMBERS CAN BE LISTED ON THE PLANS OR ON THE DESIGNER'S
 LETTERHEAD AND SIGNED AND SEALED.
  
 4) THE SLIDING GLASS DOOR PRODUCT APPROVAL (NOA
 NO.17-0420.14) IS ONLY RATED FOR SMALL MISSILE IMPACT.
 ALL GLAZED OPENINGS ARE REQUIRED TO HAVE LARGE MISSILE
 IMPACT PROTECTION PER FBC-R301.2.1.2. SUBMIT TWO SETS
 OF PRODUCT APPROVALS FOR SLIDING GLASS DOORS WITH A
 LARGE MISSILE IMPACT RATING OR PRODUCT APPROVALS FOR
 LARGE MISSILE IMPACT PROTECTION RATED STORM PANELS
 ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.
  
 5) THE MODIFIED BITUMEN ROOF SYSTEM THAT WAS SUBMITTED
 (FL5680-R15) HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF.
 THIS IS NOT ADEQUATE FOR THE PERIMETER AND CORNER AREAS
 OF THIS STRUCTURE. THIS STRUCTURE IS LOCATED IN
 EXPOSURE "D" WITH A 170 MPH VULT WINDSPEED, HAS A 5/12
 ROOF SLOPE AND HAS A MEAN ROOF HEIGHT OF 26'-9". SUBMIT
 TWO SETS OF SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS FOR THE BASE SHEET. FBC-R 301.2.1 THE RAS
 117 CALCULATIONS THAT WERE SUBMITTED ARE NOT
 ACCEPTABLE. 1) THE CALCULATIONS ARE NOT SIGNED AND
 SEALED. 2) THE PAGE NUMBER ON THE CALCULATIONS DOES NOT
 MATCH THE PAGE FROM THE PRODUCT APPROVAL THAT WAS
 MARKED AND SUBMITTED. 3) THE FASTENER SPACING SPECIFIED
 ON THE RAS CALCULATIONS FOR THE CORNERS IS LESS THAN 4"
 O.C., FBC TEST PROTOCOLS FOR RAS 117 SECTION 8.1 STATES
 THAT THE MINIMUM FASTENER SEPARATION SHALL NOT BE LESS
 THAN 4" O.C.
  
 6) SUBMIT A COPY OF THE PAID PBC IMPACT FEE RECEIPT.
 SEE IMPACT FEE REVIEW STOP.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  