Plan Review Notes
Plan Review Notes For Permit 17081337
Permit Number 17081337
Review Stop E
Sequence Number 1
Notes
Date Text
2017-09-19 08:27:03PASSED WITH PROVISO:
  
 RECEPTACLE SPACING 210.52 NEC
  
 SERVICE RECEPTACLE NEEDED IN ATTIC FOR AHU 210.63 NEC
  
 NEED BONDING BRIDGE AT SERVICE 250.94 NEC
  
 BOND GAS LINE & COLD WATER PIPE 250.104 NEC
  
 COULD NOT FIND LOCATION OF SERVICE OUTSIDE OR M.L.O.
 PANELS INSIDE ON PLAN. PROVIDE AS-BUILT SHOWING
 LOCATIONS OF SERVICE OUTSIDE AND 2, M.L.O. INTERIOR
 PANELS TO ELECTRICAL INSPECTOR ON-SITE FOR FINAL.
 INTERIOR PANELS CANNOT BE LOCATED IN BATHROOMS OR
 CLOSETS. 240.24 (D) & (E).
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  