Plan Review Notes For Permit 17081337 |
Permit Number |
17081337 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-19 08:27:03 | PASSED WITH PROVISO: | | | | RECEPTACLE SPACING 210.52 NEC | | | | SERVICE RECEPTACLE NEEDED IN ATTIC FOR AHU 210.63 NEC | | | | NEED BONDING BRIDGE AT SERVICE 250.94 NEC | | | | BOND GAS LINE & COLD WATER PIPE 250.104 NEC | | | | COULD NOT FIND LOCATION OF SERVICE OUTSIDE OR M.L.O. | | PANELS INSIDE ON PLAN. PROVIDE AS-BUILT SHOWING | | LOCATIONS OF SERVICE OUTSIDE AND 2, M.L.O. INTERIOR | | PANELS TO ELECTRICAL INSPECTOR ON-SITE FOR FINAL. | | INTERIOR PANELS CANNOT BE LOCATED IN BATHROOMS OR | | CLOSETS. 240.24 (D) & (E). | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | DEVELOPMENT SERVICES DEPT. | | CELL 561-657-1653 | | [email protected] |
|