2017-08-29 12:35:50BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RESIDENT INSPECTOR AGREEMENT REQUIRED.
 2. EOR SEAL MISSING ON PLAN PAGES SK-1 & SK-2.
  
 ADDITIONAL REVIEW COMMENTS - 9/14/17
 NOTE: THE CONTRACT, PROVIDED WITH THE PERMIT
 APPLICATION IS BETWEEN ENVIRO-TEC SERVICES INC. (GA/FL)
 LEGACY BROTHERS LLC AND FLAGLER COVE CONDOMINIUM.
  
 3. PER F.S. 713.13, THE ISSUING AUTHORITY SHALL VERIFY
 THE NAME AND ADDRESS OF THE OWNER, THE NAME OF THE
 CONTRACTOR AND THE LOCATION OR ADDRESS OF THE PROPERTY
 BEING IMPROVED WHICH IS CONTAINED IN THE CERTIFIED COPY
 OF THE NOTICE OF COMMENCEMENT IS CONSISTENT WITH THE
 INFORMATION IN THE BUILDING PERMIT APPLICATION:
 3A. THE NOTICE OF COMMENNCEMENT, LINE # 3, OWNER
 INFORMATION STATES THE OWNER AS ELIZABETH TUTEIN. THE
 CORRECT OWNER IS FLAGLER COVE CONDOMINIUM ASSOCIATION.
 PLEASE CORRECT AND RE-FILE NOC.
 3B. PERMIT APPLICATION, SECTION 2, STATES OWNER AS
 ELIZABETH TUTEIN. THE CORRECT OWNER IS FLAGLER COVE
 CONDOMINIUM ASSOCIATION. PLEASE CORRECT AND RE-SUBMIT
 PERMIT APPLICATION.
 3C. PERMIT APPLICATION, SECTION 7 STATES OWNER/AGENT AS
 JONATHAN YATES. THE OWNER/AGENT IS KEVIN O'DEA, FLAGLER
 COVE CONDOMINIUM ASSOCIATION PRESIDENT. PLEASE CORRECT
 AND RE-SUBMIT PERMIT APPLICATION.
 3D. PERMIT APPLICATION, SECTION 8 STATES CONTRACTOR AS
 KEVIN O'DEA. THE CONTRACTOR IS JONATHAN YATES DBA
 LEGACY BROTHERS LLC. PLEASE CORRECT AND RE-SUBMIT
 PERMIT APPLICATION.
  
 RESIDENT INSPECTOR
  
 CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES.
 SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 1. RESIDENT INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 2. PROVIDE RESUME OF RESIDENT INSPECTOR.
 3. PROVIDE RESUME OF JOB INSPECTOR IF DIFFERENT FROM
 RESIDENT INSPECTOR - (P.E., ARCH. OR 468 INSPECTOR).
 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 5. PROVIDE STRUCTURAL INSPECTION PLAN.
  
 FBC-107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS - THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL TO SAID
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  