Date Text
2017-09-19 12:32:271) THE SINK IN THE BREAK ROOM AND AT THE RECEPTION AREA
 SHALL COMPLY WITH THE 2014 FBC-ACCESS. SECS.212.3, 606.
 THE PLANS HAVE AN ELEVATION OF "ADA" SINK BUT IT IS
 SPECIFIED AS TO THE LOCATION OF THIS SINK.THE MAXIMUM
 HEIGHT FOR BOTH OF THESE SINKS SHALL BE 34 INCHES ABOVE
 FINISH FLOOR TO THE TOP OF THE COUNTER.
 2) AIR ARRESTORS ARE REQUIRED ON THE DISHWASHER, WATER
 DISPENSER AND THE ICE MAKER PER THE 2014 FBC-PLUMBING
 SEC.604.9.
 3) BACKFLOW PREVENTERS ARE REQUIRED ON THE COFFEE
 MACINE, WATER DISPENSER, AND ICEMAKER. 2014 FBC
 -PLUMBING SEC.608.3, 608.16.10.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE EEMAX
 INSTANT WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P-001 - SHOW THE REQUIRED HEIGHT AND KNEE AND
 TOE CLEARANCES FOR THE HANDICAPPED ACCESSIBLE
 LAVATORIES PER THE 2014 FBC-ACCESS. SECS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  