Plan Review Notes For Permit 17081230 |
Permit Number |
17081230 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-09-19 12:32:27 | 1) THE SINK IN THE BREAK ROOM AND AT THE RECEPTION AREA | | SHALL COMPLY WITH THE 2014 FBC-ACCESS. SECS.212.3, 606. | | THE PLANS HAVE AN ELEVATION OF "ADA" SINK BUT IT IS | | SPECIFIED AS TO THE LOCATION OF THIS SINK.THE MAXIMUM | | HEIGHT FOR BOTH OF THESE SINKS SHALL BE 34 INCHES ABOVE | | FINISH FLOOR TO THE TOP OF THE COUNTER. | | 2) AIR ARRESTORS ARE REQUIRED ON THE DISHWASHER, WATER | | DISPENSER AND THE ICE MAKER PER THE 2014 FBC-PLUMBING | | SEC.604.9. | | 3) BACKFLOW PREVENTERS ARE REQUIRED ON THE COFFEE | | MACINE, WATER DISPENSER, AND ICEMAKER. 2014 FBC | | -PLUMBING SEC.608.3, 608.16.10. | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE EEMAX | | INSTANT WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. | | 5) SHT. P-001 - SHOW THE REQUIRED HEIGHT AND KNEE AND | | TOE CLEARANCES FOR THE HANDICAPPED ACCESSIBLE | | LAVATORIES PER THE 2014 FBC-ACCESS. SECS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|