2017-09-13 13:00:38 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| WALK-IN COOLERS, HOODS, ETC. FBC 105.1 |
| 2. RECEPTACLE CONTROL INDICATED DOES NOT COVER ALL |
| AREAS REQUIRED. PROVIDE CORRECTION TO INCLUDE CONTROL |
| FOR AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP |
| RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, |
| ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING |
| FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL |
| WORKSTATIONS. FBC CE 405.7.1, ASHRAE 90.1:8.4.2 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |