2018-02-02 16:49:423RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17081207
 2/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. I
 HAVE REPRINTED IT BELOW. THE EMAILED PHOTO TO MY
 ATTENTION WAS NOT SUFFICIENT EVIDENCE OF THE ROOF
 SLOPE, AND PHOTOS ARE NOT ACCEPTED AS CONSTRUCTION
 DOCUMENTS.
  
 PLEASE PROVIDE A CLEAR, DIMENSIONED DRAWING THAT
 DEPICTS THE ACTUAL LOCATION AND ROOF SLOPE.
  
 3) M1.1: IT APPEARS THAT ACCESS TO THE CONDENSING UNITS
 WILL REQUIRE WALKING OVER A SLOPED ROOF. PLEASE VERIFY
 THAT THE SLOPE OF THE ROOF DOES NOT EXCEED 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33% SLOPE)- SECTION
 306.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  