Plan Review Notes For Permit 17081207 |
Permit Number |
17081207 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-11-09 11:18:27 | PLUMBING PROVISO: | | 1. BEFORE FIRST INSPECTION PROVIDE A GREASE INTERCEPTOR | | SIZING CALCULATION DONE BY SCHIER THE MANUFACTURE. WPB | | AMEND TO FBC 107.2.1.3 | | 2. A BACKFLOW IS REQUIRED ON THE SUPPLY LINE TO THE ICE | | MACHINE, COFFEE, CAPPUCCINO MACHINE AND SLURPEE, | | BEVERAGE MACHINES. PER FBC PL 608.3, 608.16.1, | | 608.16.10 | | 3. PROVIDE TRAP PRIMER FOR ALL FLOOR DRAINS. PER FBC PL | | 1002.4 | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|