Plan Review Notes
Plan Review Notes For Permit 17081207
Permit Number 17081207
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-07 12:15:141ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081207
 11/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REQUESTED AC CALCULATIONS WERE NOT PROVIDED. 2ND
 REQUEST- PLEASE COMPLY.
  
 2) PLEASE INCLUDE COMPLIANCE DATA FOR THE AC SYSTEMS ON
 THE COMCHECK ENERGY COMPLIANCE SUBMITTAL.
  
 3) M1.1: IT APPEARS THAT ACCESS TO THE CONDENSING UNITS
 WILL REQUIRE WALKING OVER A SLOPED ROOF. PLEASE VERIFY
 THAT THE SLOPE OF THE ROOF DOES NOT EXCEED 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33% SLOPE)- SECTION
 306.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved