2017-08-29 11:36:341ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM TOP OF GRIPPING
 SURFACE TO FINISH FLOOR. PER FBC ACC 609.4
  
 2. SHT. A2.1 DETAILS 2, 5, 9, AND UNDER KEY NOTE
 DETAILS 8, 9 SHOW VERTICAL GRAB BARS, GRAB BARS SHALL
 BE INSTALLED IN A HORIZONTAL POSITION ONLY. PER FBC ACC
 609.4
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH
 CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET
  
 4. PLEASE EXPAND THE WATER RISER AND LABEL ALL
 FIXTURES. WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. THE RPZ BACKFLOW DEVISE ON WATER SERVICE SHALL BE
 NEXT TO THE CITY METER PER WPB UTILITIES DEPT.
  
 6. A SEPARATE PERMIT IS REQUIRED FOR THE RPZ ON THE
 WATER SERVICE.
  
 7. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR
 GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1.
  
 8. PLEASE PROVIDE A SANITARY RISER. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 9. PLEASE SHOW ON THE RISER DIAGRAMS THE REQUIRED TRAP
 PRIMERS ON FLOOR DRAINS, THE AIR HAMMER ARRESTORS AND
 SHUT OFFS ON THE DROPS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  