2017-08-30 17:10:531ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081207
 8/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE PERMIT APPLICATION AND PLANS ARE REQUIRED
 FOR THE REFRIGERATION SYSTEMS. THIS WOULD INCLUDE THE
 SYSTEMS SHOWN ON SHEET M1.3- SANDWICH CASE AND VAULT
 COOLER, AND ANY OTHER REFRIGERATION EQUIPMENT LISTED IN
 THE SCHEDULE ON SHEET EF-1.
  
 2) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW
 CARRIER AC SYSTEMS- SECTION 312.1.
  
 3) SHEET M1.0: PLEASE CORRECTLY LABEL AHU-2 ON THE PLAN
 AND IN THE AIR HANDLING AND CONDENSING UNIT SCHEDULES.
  
 4) REFER TO SECTION 606.2.1: SMOKE DETECTORS ARE
 REQUIRED IN THE RETURN AIR SYSTEMS OF THE 5-TON CARRIER
 CASSETTE SYSTEMS UNLESS MANUFACTURER'S SPECIFICATIONS
 INDICATE THE CASSETTE GROUPS CANNOT PRODUCE SUPPLY AIR
 IN EXCESS OF 2000 CFMS. PLEASE NOTE THAT SECTION
 606.2.1 ALLOWS AN EXCEPTION FOR AREA SMOKE DETECTORS TO
 BE INSTALLED IN LIEU OF DETECTORS IN THE RETURN AIR
 SYSTEMS.
  