Plan Review Notes For Permit 17081207 |
Permit Number |
17081207 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-30 17:10:53 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17081207 | | 8/30/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) A SEPARATE PERMIT APPLICATION AND PLANS ARE REQUIRED | | FOR THE REFRIGERATION SYSTEMS. THIS WOULD INCLUDE THE | | SYSTEMS SHOWN ON SHEET M1.3- SANDWICH CASE AND VAULT | | COOLER, AND ANY OTHER REFRIGERATION EQUIPMENT LISTED IN | | THE SCHEDULE ON SHEET EF-1. | | | | 2) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW | | CARRIER AC SYSTEMS- SECTION 312.1. | | | | 3) SHEET M1.0: PLEASE CORRECTLY LABEL AHU-2 ON THE PLAN | | AND IN THE AIR HANDLING AND CONDENSING UNIT SCHEDULES. | | | | 4) REFER TO SECTION 606.2.1: SMOKE DETECTORS ARE | | REQUIRED IN THE RETURN AIR SYSTEMS OF THE 5-TON CARRIER | | CASSETTE SYSTEMS UNLESS MANUFACTURER'S SPECIFICATIONS | | INDICATE THE CASSETTE GROUPS CANNOT PRODUCE SUPPLY AIR | | IN EXCESS OF 2000 CFMS. PLEASE NOTE THAT SECTION | | 606.2.1 ALLOWS AN EXCEPTION FOR AREA SMOKE DETECTORS TO | | BE INSTALLED IN LIEU OF DETECTORS IN THE RETURN AIR | | SYSTEMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|