2017-08-30 08:58:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NOT
 INDICATED ON POWER PLAN. NEC 600.5; FBC CE 405.2.4
 2. PROVIDE ACCURATE LOAD CALCULATION. MANY ITEMS ARE
 LISTED IN PANEL SCHEDULES AND SHOW 0.00 KVA LOAD.
 UPDATE ALL SCHEDULES WITH ACCURATE INFORMATION TO SHOW
 TOTAL LOAD ON SERVICE. NEC 220; FBC 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 5. PROVIDE GFCI PROTECTED W/P OUTLET FOR SERVICING OF
 A/C EQUIPMENT ON ROOF PER CODE. NEC 210.63
 6. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 7. IN THE BATHROOMS AND BOH AREAS, IS THE SWITCH
 INDICATED AN OCCUPANCY SENSOR TYPE SWITCH? NO NOTE OR
 LEGEND IS PROVIDED. PROVIDE CLARIFICATION. FBC 107.2.1
 8. DETAIL 5 ON SHEET E2.0 SHOWS CIRCUITS CONTROLLED
 THAT ARE NOT ON ANY OF THE PLANS. PROVIDE CORRECTION.
 FBC 107.2.1
 9. CIRCUIT L-17 DOES NOT SHOW ANY MANUAL OR AUTOMATIC
 CONTROL FOR THE LIGHTING. PROVIDE CORRECTION. FBC CE
 405.2.2
 10. PROVIDE COPY OF SIGNED CONTRACT, WITH SCOPE AND
 VALUE OF WORK SHOWN. FBC 109.3
  
 PLEASE NOTE: IT APPEARS THERE IS QUITE A LOT OF MISSING
 INFORMATION WITH THIS SUBMITTAL. SUBMITTAL OF
 ADDITIONAL AND/OR REVISED MATERIALS MAY RESULT IN NEW
 PLAN REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE
 OR VOID THE PREVIOUSLY REVIEWED SHEETS.
  