Plan Review Notes For Permit 17081137 |
Permit Number |
17081137 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-10-14 12:41:51 | PROVISO | | 1. FOUNDATION - CONTRACTOR TO PROVIDE DETAIL PER MANUF. | | INSTALLATION INSTRUCTIONS, SEE SEC. 3.2 (PG'S. 24 & | | 25). | | 2. EQUIPMENT PAD ELEVATION - DFE 8' 0". | | 3. ATTACHMENT DETAIL - CONTRACTOR TO SPECIFY ANCHORS | | PER SEC. 3.2.4 (PG 25) AND RED HEAD SUBMITTAL. | | 4. VIBRATION ISOLATORS - CONTRACTOR TO SELECT ISOLATOR | | TYPE PER SEC. 3.4 (PG'S 25 & 26). |
|