Plan Review Notes For Permit 17081137 |
Permit Number |
17081137 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-25 09:50:43 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | NEED TO SUBMIT A RISER DIAGRAM BLDG PLANS 16050108 | | SHOWS 400A GENERATOR, THE PAPER WORK SHOWS 600A | | | | PAPER WORK NOT CLEAR AS TO WHAT TYPE OF GENERATOR AND | | TRANSFER SWITCH IS BEING USED (SIZE) | | | | PLEASE CLARIFY WITH ONE LINE DIAGRAM OF THE RISER ALONG | | WITH WIRE SIZES AND DISCONNECT SIZES. |
|