2017-08-25 09:50:43FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED TO SUBMIT A RISER DIAGRAM BLDG PLANS 16050108
 SHOWS 400A GENERATOR, THE PAPER WORK SHOWS 600A
  
 PAPER WORK NOT CLEAR AS TO WHAT TYPE OF GENERATOR AND
 TRANSFER SWITCH IS BEING USED (SIZE)
  
 PLEASE CLARIFY WITH ONE LINE DIAGRAM OF THE RISER ALONG
 WITH WIRE SIZES AND DISCONNECT SIZES.