Plan Review Notes
Plan Review Notes For Permit 17081093
Permit Number 17081093
Review Stop B
Sequence Number 3
Notes
Date Text
2017-12-08 15:51:46NEW GUEST HOUSE (R3) THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL PROVIDE REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS.
 REVISION FEES WILL APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME. ENERGY CALCULATIONS NEED TO BE CERTIFIED BY
 THE OWNER OR LEGAL AGENT BEFORE ISSUING THE PERMIT.
  
  
 1- ENERGY CALCULATIONS FORM R405-2014 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) CONCRETE BLOCK WALL INSULATION R-VALUE SPECIFIED ON
 ITEM #9 DOESN'T MATCH ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 D) CEILING INSULATION R-VALUE AND AREA SPECIFIED ON
 ITEM #10 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 E) PROVIDE COMPLETE INSPECTION CHECKLIST DOCUMENTING
 THE BUILDING COMPONENT CHARACTERISTICS OF THE PROPOSED
 DESIGN AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 F) PROVIDE THE NAME OF THE PERSON COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 SUBMITTED NEEDS TO BE COMPLETED BY THE BUILDER AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 H) THE "SPACES" INFORMATION ON 2 OF 4 SPECIFIES THAT
 THERE IS A KITCHEN. ACCORDING TO PLANS SUBMITTED THERE
 IS NOT KITCHEN IN THE GUEST HOUSE. THERE IS SUPPOSED TO
 BE NO COOKING. NOTE: ZONING DOESN'T ALLOW A KITCHEN FOR
 THE GUEST HOUSE. REVISE ENERGY CALCULATIONS AS
 REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 I) THE ROOF TYPE AND MATERIALS SPECIFIED ON PAGE 2 OF 4
 DON'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER TO EXPEDITE THE
 REVIEW PROCESS.
  