2017-11-02 14:49:34 | NEW GUEST HOUSE (R3) SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS THAT CONTRACTOR WILL PROVIDE REQUIRED INFORMATION |
| AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO |
| AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY. |
| CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| THIS TIME. |
| |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE SOIL TEST REPORT (2 COPIES) FOR THE AREA |
| WHERE PROPOSED TWO STORY STRUCTURE IS GOING TO BE |
| BUILT. SEC. R401.4 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| REMAINDER: ENGINEER OF RECORD TO REVIEW THE SOIL TEST |
| REPORT TO VERIFY DESIGN CRITERIA AND AVOID CONFLICTS. |
| RESPONSE: |
| REQUESTED SOIL TEST REPORT WAS NOT SUBMITTED. INSTEAD A |
| "CERTIFICATION OF SOIL COMPACTION" LETTER WAS |
| SUBMITTED. THE REQUEST WAS FOR THE SOIL TEST REPORT TO |
| BE SUBMITTED FOR REVIEW NOT FOR THE COMPACTION LETTER. |
| THE COMPACTION LETTER IS TO BE HANDLED TO THE BUILDING |
| INSPECTOR AT TIME OF SLAB INSPECTION. NEED TO SUBMIT |
| THE SOIL TEST REPORT AS REQUESTED TO VERIFY DESIGN |
| CRITERIA. ALSO, COMPACTION LETTER IS VOIDED BECAUSE THE |
| ENGINEER'S LICENSE IS SUSPENDED. NOTE: ENGINEER'S |
| LETTER WAS SENT TO THE BOARD OF ENGINEER'S FOR REVIEW. |
| |
| |
| |
| 2- ENERGY CALCULATIONS FORM R405-2014 SUBMITTED: |
| A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE |
| BOTTOM OF THE FORM AS REQUIRED BY SEC. R103.1.1.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE OWNER'S NAME AND BUILDER'S NAME. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) CONCRETE BLOCK WALL INSULATION R-VALUE SPECIFIED ON |
| ITEM #9 DOESN'T MATCH ARCHITECT'S PLANS. REVISE AS |
| REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| D) CEILING INSULATION R-VALUE AND AREA SPECIFIED ON |
| ITEM #10 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO |
| MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| E) PROVIDE COMPLETE INSPECTION CHECKLIST DOCUMENTING |
| THE BUILDING COMPONENT CHARACTERISTICS OF THE PROPOSED |
| DESIGN AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY |
| CONSERVATION. |
| |
| F) PROVIDE THE NAME OF THE PERSON COMPLETING THE |
| COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2 |
| FBC-ENERGY CONSERVATION. |
| |
| G) THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| SUBMITTED NEEDS TO BE COMPLETED BY THE BUILDER AS |
| REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION. |
| |
| H) THE "SPACES" INFORMATION ON 2 OF 4 SPECIFIES THAT |
| THERE IS A KITCHEN. ACCORDING TO PLANS SUBMITTED THERE |
| IS NOT KITCHEN IN THE GUEST HOUSE. THERE IS SUPPOSED TO |
| BE NO COOKING. NOTE: ZONING DOESN'T ALLOW A KITCHEN FOR |
| THE GUEST HOUSE. REVISE ENERGY CALCULATIONS AS |
| REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| I) THE ROOF TYPE AND MATERIALS SPECIFIED ON PAGE 2 OF 4 |
| DON'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. |
| SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| |
| ****PLEASE PROVIDE RESPONSE LETTER TO EXPEDITE THE |
| REVIEW PROCESS. |
| |