2017-11-02 14:49:34NEW GUEST HOUSE (R3) SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL PROVIDE REQUIRED INFORMATION
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES WILL APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT
 THIS TIME.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE SOIL TEST REPORT (2 COPIES) FOR THE AREA
 WHERE PROPOSED TWO STORY STRUCTURE IS GOING TO BE
 BUILT. SEC. R401.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
 REMAINDER: ENGINEER OF RECORD TO REVIEW THE SOIL TEST
 REPORT TO VERIFY DESIGN CRITERIA AND AVOID CONFLICTS.
 RESPONSE:
 REQUESTED SOIL TEST REPORT WAS NOT SUBMITTED. INSTEAD A
 "CERTIFICATION OF SOIL COMPACTION" LETTER WAS
 SUBMITTED. THE REQUEST WAS FOR THE SOIL TEST REPORT TO
 BE SUBMITTED FOR REVIEW NOT FOR THE COMPACTION LETTER.
 THE COMPACTION LETTER IS TO BE HANDLED TO THE BUILDING
 INSPECTOR AT TIME OF SLAB INSPECTION. NEED TO SUBMIT
 THE SOIL TEST REPORT AS REQUESTED TO VERIFY DESIGN
 CRITERIA. ALSO, COMPACTION LETTER IS VOIDED BECAUSE THE
 ENGINEER'S LICENSE IS SUSPENDED. NOTE: ENGINEER'S
 LETTER WAS SENT TO THE BOARD OF ENGINEER'S FOR REVIEW.
  
  
  
 2- ENERGY CALCULATIONS FORM R405-2014 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) CONCRETE BLOCK WALL INSULATION R-VALUE SPECIFIED ON
 ITEM #9 DOESN'T MATCH ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 D) CEILING INSULATION R-VALUE AND AREA SPECIFIED ON
 ITEM #10 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE COMPLETE INSPECTION CHECKLIST DOCUMENTING
 THE BUILDING COMPONENT CHARACTERISTICS OF THE PROPOSED
 DESIGN AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION.
  
 F) PROVIDE THE NAME OF THE PERSON COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 G) THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 SUBMITTED NEEDS TO BE COMPLETED BY THE BUILDER AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 H) THE "SPACES" INFORMATION ON 2 OF 4 SPECIFIES THAT
 THERE IS A KITCHEN. ACCORDING TO PLANS SUBMITTED THERE
 IS NOT KITCHEN IN THE GUEST HOUSE. THERE IS SUPPOSED TO
 BE NO COOKING. NOTE: ZONING DOESN'T ALLOW A KITCHEN FOR
 THE GUEST HOUSE. REVISE ENERGY CALCULATIONS AS
 REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 I) THE ROOF TYPE AND MATERIALS SPECIFIED ON PAGE 2 OF 4
 DON'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER TO EXPEDITE THE
 REVIEW PROCESS.
  