Plan Review Notes
Plan Review Notes For Permit 17081093
Permit Number 17081093
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-15 07:49:47CHANGED STATUS TO FAILED, 2ND SERVICVE NOT PERMITTED
 PER NEC 230.2
2017-09-18 11:50:11CONDUIT FOR M.B. PANEL MUST BE RAN UNDERGROUND OR ITS A
 VIOLATION OF NEC 230.70 (A) (1)
 NEEDS SMOKE DETECTORS FBC 314 & 315
 BOND GAS LINE AND COLD WATER PIPE NEC 250.104
  
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  