Plan Review Notes
Plan Review Notes For Permit 17081093
Permit Number 17081093
Review Stop B
Sequence Number 1
Notes
Date Text
2017-09-20 11:11:38NEW GUEST HOUSE (R3) BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS FOR THE CONSTRUCTION OF
 THE NEW 2 STORY DETACHED GUEST HOUSE. SEC. R101.5
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). NOTE: ONLY
 THE MAIN HOUSE IS A HISTORIC CONTRIBUTING BUILDING. THE
 CONSTRUCTION OF A NEW SEPARATE STRUCTURE IS NOT
 CONSIDERED HISTORIC CONTRIBUTING. THEREFORE, ENERGY
 CALCULATIONS ARE REQUIRED.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) FOR THE AREA
 WHERE PROPOSED TWO STORY STRUCTURE IS GOING TO BE
 BUILT. SEC. R401.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- ARCHITECT TO PROVIDE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE HEATING REQUIREMENTS OF
 SEC. R303.9 FBC-RESIDENTIAL.
  
 5- GENERAL NOTE #4 ON SHEET A.01 REFERENCES 2010 CODE.
 THE CURRENT CODE IS THE FBC, 5TH EDITION (2014). REVISE
 AS REQUIRED. CHAPTER 553 F.S.
  
 6- SPECIFY ATTIC ACCESS SIZE AS REQUIRED BY R807
 FBC-RESIDENTIAL.
  
 7- THE SIZE OF FIRST FLOOR ENTRY DOOR NEEDS TO COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC. R311.2
 FBC-RESIDENTIAL.
  
 8- SPECIFY THE SIZE OF THE POWDER ROOM DOOR. SEC.
 R320.1 FBC-RESIDENTIAL.
  
 9- FLOOR PLAN NOTE #11 ON SHEET A.02 REFERENCES THE
 2010 FBC. THE CURRENT CODE IS THE FBC, 5TH EDITION
 (2014). REVISE AS REQUIRED. CHAPTER 553 F.S. SEE 2014
 FBC-RESIDENTIAL AND REFERENCE THE CORRECT CODE SECTION.
  
 10- FLOOR PLANS ON SHEET A.02 DON'T PROVIDE ANY
 INFORMATION ABOUT THE HANDRAILS REQUIRED FROM FIRST
 FLOOR TO SECOND FLOOR. SPECIFY HANDRAILS LOCATION AND
 PROVIDE COMPLETE SPECIFICATIONS SHOWING COMPLIANCE WITH
 SEC. R311.7.8 FBC-RESIDENTIAL.
  
 11- A PERMIT APPLICATION IS REQUIRED FOR EACH
 STRUCTURE. PROVIDE A SEPARATE PERMIT APPLICATION FOR
 THE WORK TO BE PERFORMED ON THE MAIN HOUSE. SEC. 105.1
 CITY AMENDMENTS. NOTE: SAME PLANS CAN BE USED FOR BOTH
 STRUCTURES. THIS IS REQUIRED FOR PROPER INSPECTIONS ON
 EACH STRUCTURE AND PROPER RECORDS RETENTION.
  
 12- WALL SECTION 11/D3 DOESN'T MATCH PROPOSED FLOOR
 PLAN ON SHEET A.04. REVISE ROOF TYPE AND FOOTINGS.
 ALSO, IT LOOKS LIKE THE EXTENSION IS GOING TO BE ON A
 STEM WALL. REVISE AS REQUIRED TO MATCH. CLARIFY WHY
 SPECIFYING SOFFIT VENT IF USING "R30" ICYNENE
 INSULATION UNDER THE ROOF SHEATHING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- PROPOSED LAUNDRY ROOM FLOOR PLAN ON SHEET A.04
 DOESN'T SHOW THE LOCATION OF THE CONCRETE BLOCK
 VERTICAL REINFORCEMENT. SPECIFY LOCATION OF THE
 REQUIRED VERTICAL REINFORCEMENT. SEC. R606.13
 FBC-RESIDENTIAL.
  
 14- WINDOW IN EXISTING BATHROOM OF THE MAIN HOUSE IS
 CLOSED TO ALLOW FOR THE LAUNDRY ADDITION. SPECIFY HOW
 THE EXISTING BATHROOM IS GOING TO BE VENTILATED AS
 REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL AND SEC.
 M1507.4 FBC-RESIDENTIAL.
  
 15- ROOF FRAMING PLAN ON SHEET S.01: SPECIFY ALL
 STRUCTURAL BEAMS AND HEADERS. SEC. R301.1
 FBC-RESIDENTIAL. PLANS DON'T SHOW TYPE OF BEAMS SHOWN
 ON THE BEAM SCHEDULE.
  
 16- SPECIFY THE DESIGN PRESSURES FOR ALL EXTERIOR DOORS
 AND WINDOWS. TABLE R301.2(2) FBC-RESIDENTIAL. WHERE IS
 THE TABLE D-1 THAT IS REFERENCED ON THE DESIGN LOADS ON
 SHEET S.01.
  
 17- ROOF FASTENING SCHEDULE DETAIL 7/D1 ON SHEET D.01:
 REVISE THE DIMENSION FOR THE GABLE END. ACCORDING TO
 TABLE R803.2.3.1 FBC-RESIDENTIAL, THEM MINIMUM
 DIMENSION IS 5'-0" NOT 4'-0". REVISE AS REQUIRED.
  
 18- REVISE STRUCTURAL CRITERIA INFORMATION ON SHEET
 D.01. THIS BUILDING IS LOCATED IN THE WINDBORNE DEBRIS
 REGION NOT IN THE NON-WINDBORNE DEBRIS REGION. FIGURE
 R301.2(4) FBC-RESIDENTIAL.
  
 19- REVISE THE STUCCO THICKNESS SPECIFIED ON THE WALL &
 ROOF FRAMING NOTES ON SHEET D.01. THE MINIMUM THICKNESS
 IS 7/8" AS REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL.
  
 20- DETAIL 3/D3 ON SHEET D.03: SPECIFY STAIRS RISERS
 AND TREADS TO SHOW COMPLIANCE WITH SEC. R311.7.5
 FBC-RESIDENTIAL.
  
 21- PROVIDE ROOF AND SECOND FLOOR ANCHOR SCHEDULE. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 22- PROVIDE SURFACE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH SEC. R401.3 FBC-RESIDENTIAL.
  
 23- TYPICAL TWO STORY WALL DETAIL 7/D4 ON SHEET D.04:
 A) THIS SECTION REFERENCES DETAIL 3/D5 . WHERE IS THIS
 DETAIL?. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) CONCRETE SLAB SPECIFICATIONS DON'T MATCH
 SPECIFICATIONS SHOWN ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED TO MATCH. SEC.107.2.1 CITY AMENDMENTS.
  
 C) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL. NOTE: THIS APPLIES TO ONE STORY WALL
 SECTION ALSO.
  
 24: PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) SLIDING GLASS DOORS: NOA 16-0629.07 SUBMITTED IS
 MISSING DRAWINGS 2, 3 AND 4 OF 19. SUBMIT MISSING
 DRAWINGS.
  
 B) FRENCH DOOR: NOA 14-1117.05 SUBMITTED IS MISSING
 DRAWINGS 1, 2,3 AND 4 OF 12. SUBMIT MISSING DRAWINGS.
  
 C) SINGLE HUNG WINDOWS. NOA 16-0714.06 SUBMITTED IS
 MISSING DRAWINGS 3, 4 AND 5 OF 11. SUBMIT MISSING
 DRAWINGS.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 NUMBER AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ARCHITECT OF RECORD TO LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 25- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS. NOTE: CLARIFY WHY APPROVING PRODUCT
 APPROVALS FOR FIXED WINDOWS AND ALUMINUM MULLIONS IF
 PLANS DON'T SPECIFY THEM.
  
 26- CLARIFY WHY SUBMITTING NOA 15-0519.15 FOR FIXED
 CASEMENT WINDOWS AND NOA 16--0218.03 FOR ALUMINUM
 MULLIONS. PLANS DON'T SHOW THIS TYPE OF WINDOW OR
 MULLIONS. ALSO. THESE NOA'S ARE MISSING SOME OR ALL
 DRAWINGS. SEC. 107.2.1 CITY AMENDMENTS.
  
 27- PRODUCT APPROVALS NUMBERS LISTED ON SHEET A.02
 DON'T MATCH PRODUCT APPROVALS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. FAC 61G20-3.001
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  