Plan Review Notes For Permit 17081008 |
Permit Number |
17081008 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-10-05 14:42:58 | 10/5/17 2ND GAS REVIEW**DENIED** | | | | 1) THE P.E RONALD WILSON LIC #9710 LICENSE HAS BEEN | | REVOKED SINCE 02/28/2017. ALSO ALL SIGNATURES ARE | | REQUIRED TO BE WET (NO COPIES) PER FL ADMIN CODE | | 61G15-23.001. PLEASE RESUBMIT | | | | 2) YOU ARE STILL MISSING THE SIZING TABLE FOR THE | | SCHEDULE 40 METALLIC PIPE AS A .5LB PLEASE SUBMIT THE | | PROPER TABLE FBC-G 402.3 | | | | 3) PROVIDE MANUFACTOR SPECS FOR EXISTING GAS REGULATOR | | AS THIS IS NOT A LIKE FOR LIKE SYSTEM. CITY RECORDS | | SHOW A SMALLER EXISTING GENERATOR INSTALLED IN 2006 |
|