2017-10-05 14:42:5810/5/17 2ND GAS REVIEW**DENIED**
  
 1) THE P.E RONALD WILSON LIC #9710 LICENSE HAS BEEN
 REVOKED SINCE 02/28/2017. ALSO ALL SIGNATURES ARE
 REQUIRED TO BE WET (NO COPIES) PER FL ADMIN CODE
 61G15-23.001. PLEASE RESUBMIT
  
 2) YOU ARE STILL MISSING THE SIZING TABLE FOR THE
 SCHEDULE 40 METALLIC PIPE AS A .5LB PLEASE SUBMIT THE
 PROPER TABLE FBC-G 402.3
  
 3) PROVIDE MANUFACTOR SPECS FOR EXISTING GAS REGULATOR
 AS THIS IS NOT A LIKE FOR LIKE SYSTEM. CITY RECORDS
 SHOW A SMALLER EXISTING GENERATOR INSTALLED IN 2006