Plan Review Notes For Permit 17081008 |
Permit Number |
17081008 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-10-06 07:48:05 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE | | THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | ACCEPTABLE. FAC 61G15 - 23.002 | | | | 2) THE ENGINEER, RONALD H. WILSON, THAT IS ON THE | | AMERICAST PAD ANCHORING PLAN HAS HAD HIS FLORIDA PE | | LICENSE REVOKED. THE SIGNATURE ON THE PLAN IS NOT AN | | ORIGINAL HANDWRITTEN ONE AS REQUIRED BY FAC | | 61G15-23.002. | | |
|