2017-10-06 07:48:05PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE
 THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002
  
 2) THE ENGINEER, RONALD H. WILSON, THAT IS ON THE
 AMERICAST PAD ANCHORING PLAN HAS HAD HIS FLORIDA PE
 LICENSE REVOKED. THE SIGNATURE ON THE PLAN IS NOT AN
 ORIGINAL HANDWRITTEN ONE AS REQUIRED BY FAC
 61G15-23.002.
  