Plan Review Notes
Plan Review Notes For Permit 17081008
Permit Number 17081008
Review Stop G
Sequence Number 1
Notes
Date Text
2017-08-28 15:01:30GAS 1ST REVIEW DENIED 8/28/17
  
 1) PROVIDE WHICH GAS IS BEING USED. GAS RISER IS
 SHOWING NATURAL GAS WHILE SIZING CHARTS PROVIDED ARE
 FOR L.P (FBC 107.1)
  
 2) PROVIDE CORRECT SIZING CHARTS THAT COMPLY WITH 402.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  