2017-08-28 10:57:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE
 THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT
 ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE
 ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS
 AND DOCUMENTS.
  
 2) THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH
 A 170 MPH WIND SPEED. PROVIDE THE REQUIRED DESIGN
 PRESSURES FOR THE GENERATOR ANCHORING. THE PRESSURES
 INDICATED ON THE GENERATOR PAD DOCUMENTS ARE NOT
 ADEQUATE. FBC-R301.2.1
  
 3) THE PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE GENERATOR EQUIPMENT IS REQUIRED TO BE LOCATED
 ONE FOOT ABOVE THE BFE, WHICH WILL BE 8 FEET NGVD.
 FBC-R322.1.6