2017-08-28 10:57:46 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD CALCULATIONS ARE REQUIRED TO HAVE | | THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN | | SIGNATURE, COPIES OR OTHER FACSIMILES ARE NOT | | ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES ARE | | ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED PLANS | | AND DOCUMENTS. | | | | 2) THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH | | A 170 MPH WIND SPEED. PROVIDE THE REQUIRED DESIGN | | PRESSURES FOR THE GENERATOR ANCHORING. THE PRESSURES | | INDICATED ON THE GENERATOR PAD DOCUMENTS ARE NOT | | ADEQUATE. FBC-R301.2.1 | | | | 3) THE PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA. THE GENERATOR EQUIPMENT IS REQUIRED TO BE LOCATED | | ONE FOOT ABOVE THE BFE, WHICH WILL BE 8 FEET NGVD. | | FBC-R322.1.6 |
|