Plan Review Notes For Permit 17080930 |
Permit Number |
17080930 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-25 16:24:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS INSUFFICIENT DETAIL TO MAKE DETERMINATIONS | | REGARDING THE FLORIDA FIRE PREVENTION CODE. | | | | | | 2) IS THERE EXISTING FIRE SPRINKLER PROTECTION? | | | | PROVIDE NOTE. | | | | | | 3) ARE THERE ANY FIRE/SMOKE DETECTION ALARMS IN THE | | AREAS OF CONSTRUCTION. | | | | PLEASE PROVIDE NOTE OF REPLACEMENT OR NEW INSTALLATION | | PER THE FFPC. | | | | | | 4) WHAT TYPE OF NEW FLOOR IS BEING INSTALLED? IS THERE | | ANY NOISE UNDERLAYMENT? PROVIDE PRODUCT SPEC SHEETS FOR | | REQUIRED INTERIOR FLAME AND SMOKE RATINGS? | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|