2017-09-22 17:45:12 | ****CORRECTIONS**** |
| REVISED 9/27/17 |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| FROM PREVIOUS LIST: |
| |
| 3) SHEET A1.01 THE DEMO NOTE # 4 INDICATES THE REMOVAL |
| OF THE FINISH FLOOR IN THE ATHLETIC ROOM. THE FINISH |
| FLOOR SCHEDULE INDICATES THE FINISH FLOOR TO BE ECORE |
| COMMERCIAL/ECO FIR RUBBER FLOORING/ GRANITE RUN 905. |
| |
| 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH |
| AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN |
| AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A |
| HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE |
| MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE |
| THE INTERIOR FLOOR FINISH OR FLOOR COVERING |
| CLASSIFICATION ACCORDING TO SECTION 804.2. |
| |
| 2ND REVIEW, A "CERTIFICATE OF COMPLIANCE" WAS PROVIDED, |
| BUT THIS CITES ASTMD2859. FLOORING OTHER THAN THOSE OF |
| A "TRADITIONAL NATURE" ARE TO BE TESTED TO NFPA 253. |
| TESTING TO ASTM D 2859 IS ALSO REQUIRED. |
| |
| IT IS NOT CLEAR WHICH OF THE FLOORING IS PROPOSED; THE |
| ONE LISTED ON THE PLAN IS NOT LISTED ON THE CERTIFICATE |
| OF COMPLIANCE. |
| |
| PROVIDE COPIES OF THE TEST REPORTS (NFPA 253, ASTM D |
| 2859). INDICATE WHICH FLOORING IS PROPOSED BY EITHER |
| REVISING THE PLAN TO INCLUDE THE NAME CONSISTENT WITH |
| THE TEST REPORTS, OR PROVIDE SPEC SHEETS AND MARK THE |
| FLOORING PROPOSED. PER FBC B 804.3, THE MANUFACTURER |
| AND STYLE SHOULD BE CONSISTENT WITH THE TEST REPORTS. |
| |