2017-08-23 07:45:40 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17080859 |
| ADD: 1801 S. FLAGLER DR. FLOOR/ SUITE: UNKNOWN |
| CONT: PHILIP E. JOHNSON |
| TEL: 561-366-1034 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED./ AUGUST 23/ 2017 |
| ACTION: DENIED |
| |
| 1) THE PERMIT NOR THE PLANS PROVIDE THE LOCATION , ON |
| WHAT FLOOR THIS WORK IS TO OCCUR. THIS IS A HIGH-RISE |
| BUILDING! |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2 CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED. |
| |
| 2) THE DESIGNER OF RECORD NEEDS TO PROVIDE TO WHICH |
| DESIGN METHOD WAS USED IN DESIGNING THE PLANS. 2014 |
| FBC-EXISTING BUILDING CODE SECTION 301.1 GENERAL. |
| THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION |
| OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY |
| WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 |
| THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. |
| |
| 3) SHEET A1.01 THE DEMO NOTE # 4 INDICATES THE REMOVAL |
| OF THE FINISH FLOOR IN THE ATHLETIC ROOM. THE FINISH |
| FLOOR SCHEDULE INDICATES THE FINISH FLOOR TO BE ECORE |
| COMMERCIAL/ECO FIR RUBBER FLOORING/ GRANITE RUN 905. |
| THE PLANS DO NOT PROVIDE WHAT FLOOR THE WORK IS TO |
| OCCUR. WHEN FLOORING IS ABOVE THE 1ST FLOOR THE CODE |
| REQUIRES COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND |
| AND 1207.3 STRUCTURE-BORNE SOUND. PLEASE PROVIDE THE |
| MANUFACTURERS SPECIFICATIONS FOR THIS PRODUCT. |
| IT WOULD APPEAR SINCE THIS IS A FINISH FLOOR MATERIAL |
| THE FLOOR CLASSIFICATION NEEDS TO BE ESTABLISHED TO BE |
| EITHER A CLASS I OR II MATERIALS AND SHALL BE |
| CLASSIFIED IN ACCORDANCE WITH NFPA 253. |
| |
| 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH |
| AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN |
| AGENCY IN ACCORDANCE WITH NFPA 253 AND IDENTIFIED BY A |
| HANG TAG OR OTHER SUITABLE METHOD SO AS TO IDENTIFY THE |
| MANUFACTURER OR SUPPLIER AND STYLE, AND SHALL INDICATE |
| THE INTERIOR FLOOR FINISH OR FLOOR COVERING |
| CLASSIFICATION ACCORDING TO SECTION 804.2. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |