Plan Review Notes
Plan Review Notes For Permit 17080857
Permit Number 17080857
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-08-22 17:04:44PROVISO: PROVIDE SPECIFICATION/CUT SHEETS FOR TANKS,
 PIPING AND APPURTENANCES.
  
 6.3.5.1.2 AT LEAST 380 MM (15 IN.) CLEARANCE SHALL BE
 LEFT AROUND EACH TANK FOR THE PURPOSE OF INSPECTION AND
 REPAIR.
  
 6.3.5.2 EACH TANK ROOM SHALL BE PROVIDED WITH AN
 OPENING THAT IS PROTECTED BY A SELF-CLOSING
 1-HOUR-RATED FIRE DOOR IF IT OPENS INSIDE A BUILDING.
  
  
 NFPA 704 SIGNAGE REQUIRED.
  
 INSTALLATION SHALL COME INTO COMPLIANCE WITH NFPA 1,
 30, 37, 70.
  
 CONSIDER THE FOLLOWING NFPA CODES WHEN SUBMITTING PLANS
 FOR STANDBY POWER. NFPA 37 & 110.
  