Plan Review Notes For Permit 17080798 |
Permit Number |
17080798 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2018-06-04 16:27:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 107, PROVIDE DIMENSIONS ON THE PLAN. WIDTH, | | HEIGHT, LENGTH NOT CLEAR. | | | | 2. FBC B 1609, WIND PRESSURES ARE TOO LOW FOR A ROOF, | | REVISE. | | | | 3. THE WALL PANELS HAVE A PRODUCT APPROVAL FOR USE AS A | | WALL PANEL; APPROVAL DOES NOT INCLUDE USE AS A ROOF. | | PROVIDE AN ENGINEERING ANALYSIS FOR USE IN HORIZONTAL | | ORIENTATION. | | | | 4. PROVIDE A PRODUCT APPROVAL FOR THE ROOF ASSEMBLY | | PROPOSED FOR THE ROOF COVERING, FBC B 1609. | | | | 5. PROVIDE A ROOF FRAMING DETAIL, FBC B 1609. ROOF | | SLOPE IS REQUIRED; SHOW ROOF SLOPE ON THE PLAN. WATER | | CANNOT DISCHARGE TO THE ADJACENT PROPERTY. | | | | 6. FBC B TABLE 503, REVISE PLAN TO SHOW COMPLIANCE WITH | | BUILDING HEIGHT AND AREA. SINCE THIS IS BUILT IN PLACE | | STORAGE ROOM RATHER THAN REMOVABLE EQUIPMENT, THIS ACTS | | AS AN EXTENSION (ADDITION) TO THE EXISTING BUILDING. | | | | 7. FBC B TABLE 602, FIRE RESISTANCE RATING REQUIRED FOR | | THE WALL ON THE PROPERTY LINE. | | |
|