2017-08-22 06:29:44 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17080798 |
| ADD: 425 25TH ST. |
| CONT: A & S REFRIGERATION & AIR |
| TEL: 561-793-9698 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUG. 22/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE WIND DESIGN DATA AND ASSOCIATED |
| PRESSURES. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 1.2. RISK CATEGORY. |
| |
| 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| |
| 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 2) PLEASE PROVIDE EITHER A FLORIDA STATE APPROVED |
| MODULAR BUILDING (COOLER/ FREEZER) UNDER FLORIDA |
| ADMINISTRATIVE CODE 61-41 MANUFACTURERED BUILDING |
| PROGRAM OR ENGINEERED PLANS FOR THIS WIND SPEED ZONE. |
| |
| 3) PROVIDE A SITE PLAN FOR LOCATION ON LOT. 107.2.1.3. |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |