2017-11-09 16:43:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080793
 11/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) RESIDENTIAL MANUAL J CALCULATIONS CANNOT BE
 SUBMITTED FOR COMMERCIAL AC SYSTEMS. PLEASE REFER TO
 SECTION C403.2.1 CALCULATION OF HEATING AND COOLING
 LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT.
  
 2) PLEASE NOTE THAT THE MANUAL J CALCULATION
 INCORRECTLY INDICATES THE "FRONT DOOR FACING NORTH"
 HOWEVER THE FRONT DOOR IS FACING SOUTH.
  
 3) THE COMCHECK COMPLIANCE CERTIFICATE INDICATES 16
 SEER SYSTEMS, HOWEVER 14 SEER SYSTEMS ARE SHOWN IN THE
 AC SCHEDULE- PLEASE CORRECT.
  
 4) THE REQUESTED MIAMI-DADE NOA FOR THE ROOF STAND WAS
 NOT SUBMITTED. PLEASE NOTE THAT THE PREVIOUSLY
 SUBMITTED NOA DID NOT HAVE THE RIGHT INSTALLATION
 DRAWINGS ATTACHED WITH THE COVER SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  