2017-10-23 17:30:463RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17080793
 10/23/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED PLAN APPEARS TO SHOW NEW ROUND
 OUTSIDE AIR DUCTS GOING THROUGH THE ROOF HOWEVER THEY
 ARE LABELED AS R/A (RETURN AIR) DUCTS AND THE SIZES OF
 THESE DUCTS ARE NOT INDICATED- PLEASE CORRECT.
  
 2) THE RESUBMITTED PLAN IS NOW INDICATING 765 CFMS OF
 O/A FOR THE 5-TON SYSTEM WHICH IS 38% OF THE TOTAL 2000
 CFM SUPPLY CFMS. BY INDUSTRY STANDARDS THIS WOULD BE
 CONSIDERED A LARGE AMOUNT OF O/A TO BE CONSTANTLY
 COOLED BY A 5-TON SYSTEM. PLEASE NOTE THAT A TEST AND
 BALANCE REPORT MUST BE SUBMITTED TO VERIFY THE O/A
 AMOUNT AND THE AIR DISTRIBUTION AS DESIGNED- SEE NOTE
 #13 ON SHEET M-1.
  
 3) SHEETS M-1 & M-2: THE ARCHITECT IS INDICATING THAT
 THE ROOF TOP CONDENSER "SHALL BE INSTALLED TO RESIST
 WIND PRESSURES AT VELOCITIES INDICATED ON FBCM 301.15".
 PLEASE NOTE THAT THE MECHANICAL CODE SECTION 301.15
 REFERENCES THE FLORIDA BUILDING CODE FOR WIND DESIGN,
 AND DOES NOT PROVIDE ANY DESIGN PRESSURES- PLEASE
 CORRECT AND PROVIDE ACCURATE WIND LOAD DESIGN CRITERIA
 . AS PREVIOUSLY REQUESTED, SUBMIT THE MIAMI-DADE NOA,
 OR THE FLORIDA PRODUCT APPROVAL FOR THE AC STAND WITH
 APPROVAL STAMP BY THE ARCHITECT OF RECORD.
  