Date |
Text |
2017-10-03 14:22:13 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| |
| 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES |
| SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS |
| TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN |
| AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND |
| NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR |
| SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE |
| WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN |
| 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND |
| THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE |
| FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER |
| FBC PL 405.3.5 URINAL STILL SHOWN ON ADA DETAIL AND |
| NOTES. SHT.A-1 + P-2 PLEASE REMOVE |
| |
| 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S. |
| PER FBC ACC 606.2 |
| |
| 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE |
| IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 AAV STILL SHOWN IN MIDDLE OF FLOOR |
| ON BRANCH DRAIN FOR SERVICE SINK NOT A REQUIRED VENT |
| |
| 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT |
| LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1 |
| |
| 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY |
| WATER METER. PER WPB UTILITIES PLEASE SHOW BACKFLOW |
| NEXT TO METER ON RISER AND FLOOR PLAN. |
| |
| NEW COMMENTS: |
| |
| 1. PLEASE LABEL FLORIDA ACCESSIBILITY CODE NOTES ON |
| SHT. P-1. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHUT OFF VALVES ARE REQUIRED ON EACH DROP ON WATER |
| PIPING. PER FBC PL 606.1 LOCATION OF FULL-OPEN VALVES. |
| FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE |
| IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY |
| RESIDENTIAL OCCUPANCIES. |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |