Plan Review Notes
Plan Review Notes For Permit 17080793
Permit Number 17080793
Review Stop P
Sequence Number 2
Notes
Date Text
2017-10-03 14:22:132ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES
 SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS
 TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE
 WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN
 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND
 THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER
 FBC PL 405.3.5 URINAL STILL SHOWN ON ADA DETAIL AND
 NOTES. SHT.A-1 + P-2 PLEASE REMOVE
  
 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S.
 PER FBC ACC 606.2
  
 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE
 IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1 AAV STILL SHOWN IN MIDDLE OF FLOOR
 ON BRANCH DRAIN FOR SERVICE SINK NOT A REQUIRED VENT
  
 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT
 LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY
 WATER METER. PER WPB UTILITIES PLEASE SHOW BACKFLOW
 NEXT TO METER ON RISER AND FLOOR PLAN.
  
 NEW COMMENTS:
  
 1. PLEASE LABEL FLORIDA ACCESSIBILITY CODE NOTES ON
 SHT. P-1. PER WPB AMEND TO FBC 107.2.1
  
 2. SHUT OFF VALVES ARE REQUIRED ON EACH DROP ON WATER
 PIPING. PER FBC PL 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE
 IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY
 RESIDENTIAL OCCUPANCIES.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved