2017-09-28 14:12:25 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY |
| CONSERVATION CODES |
| PERMIT #17080793 |
| 9/28/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE RESCHECK COMPLIANCE SUBMITTAL IS INDICATING THE |
| PROJECT TYPE TO BE A "MULTI-FAMILY", HOWEVER THE |
| PROPOSED PROJECT IS CHANGE OF OCCUPANCY FROM MERCANTILE |
| TO ASSEMBLY AND MUST BE IN COMPLIANCE WITH THE |
| COMMERCIAL CODES. PLEASE SEE SECTION C101.5.1 FBC-14 |
| ENERGY CONSERVATION AND PROVIDE EITHER A FLORIDA |
| ENERGYGAUGE COMPLIANCE SUBMITTAL OR A COMCHECK |
| COMPLIANCE CERTIFICATE. |
| |
| 2) M-2: THE 5-TON AC SYSTEM WHICH IS PRESUMED TO |
| PRODUCE APPROXIMATE 2000 CFMS WOULD BE UNDERSIZED TO |
| CONDITION 1040 CFMS OF OUTSIDE AIR ACCORDING TO |
| ASHRAE/ACCA STANDARDS. THE TYPICAL PERCENTAGE OF |
| OUTSIDE AIR TO SUPPLY AIR WOULD RANGE AROUND 17-20%. IN |
| ADDITION THE 14X12 DUCT THAT IS BOTH SUPPLYING THE O/A |
| AND RETURNING 1370 CFMS OF AIR FROM THE SPACE IS |
| UNDERSIZED FOR THE TOTAL 2410 CFMS OF AIR- PLEASE |
| CORRECT. |
| |
| 3) M-2, AC EQUIPMENT SCHEDULE: PROVIDE THE KW |
| CAPACITIES OF THE AIR HANDLER HEAT STRIPS AND THE TOTAL |
| SUPPLY CFMS OF EACH SYSTEM. |
| |
| 4) M-2: THE OUTSIDE AIR INLETS APPEAR TO BE WITHIN THE |
| REQUIRED 10' CLEARANCE SPACE TO THE ADJACENT OPEN |
| PARKING AREA- SEE SECTION 401.4 AND CORRECT. |
| |
| 5) M-1: THE REQUESTED WIND LOAD ENGINEERING AND NOA FOR |
| THE AC STANDS WAS NOT PROVIDED. PROVIDE ON THE PLAN THE |
| WIND DESIGN CRITERIA USED TO DETERMNINE THE DESIGN |
| PRESSURES AND TIE DOWN REQUIREMENTS- SEESECTION 301.15 |
| FBC-14 MECH. & 1609 FBC-14 BUILDING. |
| |
| 6) PROVIDE THE MIAMI-DADE NOAS OR FLORIDA PRODUCT |
| APPROVALS FOR THE ROOF STANDS AND LOUVERS- RULE 9N-3 |
| FAC. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |