2017-09-28 17:52:21 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN | | THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2 | | SEE FBC CODE SECTION 405.2.2.FOR THE ADDITIONAL | | REQUIREMENT FOR OCUUPANCY SENSORS IN ADDITION TO MANUAL | | CONTROL IN ALL AREAS. | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | |
|