Plan Review Notes
Plan Review Notes For Permit 17080793
Permit Number 17080793
Review Stop E
Sequence Number 2
Notes
Date Text
2017-09-28 17:52:21FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2
 SEE FBC CODE SECTION 405.2.2.FOR THE ADDITIONAL
 REQUIREMENT FOR OCUUPANCY SENSORS IN ADDITION TO MANUAL
 CONTROL IN ALL AREAS.
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
  