2017-09-27 08:03:13 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17080793 |
| ADD: 329 CLEMATIS ST. SUITE: B |
| CONT: DURHAM BROTHERS |
| TEL: 561-662-0736 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. SEPT. 27/ 2017 |
| ACTION: DENIED |
| |
| 1) COMPLIED. SITE THE OLD MYERS LUGGAGE STORE. A CHANGE |
| OF OCCUPANCY TO A A2 |
| |
| 1A)SEMI-COMPLIED. SHEET A-1 THE EAST 6 INCH FRAME WALL |
| WILL NEED TO PROVIDE EITHER A U. L. LISTING, OR GYPSUM |
| ASSOCIATION LISTING, WITH TYPE OF FRAMING MEMBER, |
| SPACING OF FRAMING MEMBER, TYPE OF DRYWALL, THICKNESS |
| AND LAYERS TO COMPLETE THE WALL ASSEMBLY FOR A 2 HOUR |
| FIRE RATING. . FBC-B 707.3.9 SEPARATED OCCUPANCIES & |
| 707.5 CONTINUITY.1ST ROUND OF COMMENTS. THE COVERSHEET |
| DOES NOT PROVIDE THE REQUIRED OCCUPANCY SEPARATION |
| REQUIREMENT FOUND IN TABLE 508.4 OF THE 2014 FBC-B. |
| SHEET A-1 DOES INDICATE EXISTING 2 HR. OCCUPANCY |
| SEPARATION BUT DOES NOT DECLARE THE TYPE OF WALL |
| ASSEMBLY TO MAKE UP THE EXISTING 2 HR. FIRE BARRIER. |
| FBC-B 707.3.9 SEPARATED OCCUPANCIES & 707.5 CONTINUITY. |
| |
| 1B) COMPLETED. |
| |
| 1C) 2ND REQUEST. SHEET A-1 RESTATES THE CODE SECTION |
| MANY TIMES, DOES NOT SHOW CODE COMPLIANCE. 2014 FLORIDA |
| BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 1ST ROUND COMMENT. PLEASE PROVIDE COMPLIANCE WITH THE |
| 2014 FBC-EXISTING BUILDING CODE SECTION 1012.1.2 FIRE |
| PROTECTION AND INTERIOR FINISH. THE PROVISIONS OF |
| SECTIONS 1012.2 AND 1012.3 FOR FIRE PROTECTION AND |
| INTERIOR FINISH, RESPECTIVELY, SHALL APPLY TO ALL |
| BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION. |
| |
| 1D) 2ND REQUEST. PLEASE NOTE THE SEATING AGAINST THE |
| EAST WALL HAS BEEN ELIMINATED, NOT SHOWING ANY DENSITY |
| WILL TAKE THE MOST RESTRICTIVE AT 5 SQ. FT./ OCCUPANT. |
| PLEASE REVIEW UNDER CHAPTER 10 OF THE EXISTING BUILDING |
| CODE THE REQUIREMENT FOR FIRE SPRINKLERS. 2014 EXT. |
| BLDG. CODE 1012.2 FIRE PROTECTION SYSTEMS. |
| FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTIONS 1012.2.1 AND 1012.2.2. |
| EXST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE |
| A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. |
| 2014 FBC-B SECTION F] 903.2.1.2 GROUP A-2. AN AUTOMATIC |
| SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2 |
| OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR |
| MORE. |
| |
| 2) SHEET A-1: |
| 2A-B) COMPLIED. |
| |
| 2C) 2ND REQUEST. SHEET A1 SHOWS 4 ACCESSIBLE SEATS. THE |
| LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE : |
| 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING |
| SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| WITH 902. 80 SEATS X 0.05= 4.0 OR 4 SEATS,3 SHOWN ON |
| PLANS. |
| |
| 2D) 2ND REQUEST, NO DROPPED PORTION OF BAR FOR |
| HANDICAPPED SEATING AT BAR. FBC-ACCESSIBILITY CODE |
| 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| SURFACES AND WORK SURFACES. THE PLANS DO NOT SHOW |
| COMPLIANCE WITH: 902.1 .DINING SURFACES AND WORK |
| SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY |
| 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT |
| LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| |
| 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND |
| 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 2E) COMPLIED. |
| |
| 3) COMPLIED. |
| |
| 4) 2ND REQUEST. NOTE THE ARCHITECT OF RECORD IS SIGNING |
| AND SEALING COMPUTER SOFTWARE PROGRAM. PLEASE BE AWARE |
| WITHIN THE SOFTWARE GROGRAM YOU HAVE TAKEN CREDIT FOR 3 |
| FOOT PARAPETS ON ALL SIDES OF THE ROOF. ON THE NORTH |
| AND EAST SIDES OF THE BUILDING THERE IS NO 3 FOOT |
| PARAPET, PLEASE CORRECT THE INPUT DATA TO PROVIDE |
| PRESSURES FOR ROOF ZONE 3. GOOGLE EARTH AND A |
| COUNTYWIDE GIS PROGRAM ALLOWS FOR AERIAL VIEWS OF |
| BUILDINGS. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF |
| MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| 1609.7.2. HEIGHT AND EXPOSURE. |
| |
| THE MECA SOFTWARE PROGRAM SUBMITTED IS VERY LIGHT, HARD |
| TO READ AND WILL NOT MEET THE QUALITY OF PLANS |
| REQUIRED, FOR SCANNING INTO RECORD RETENTION. 107.2.1.4 |
| QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| |
| THE 3RD ISSUE WITH THE ARCHITECT SIGNING AND SEALING |
| THE WIND DESIGN REPORT IS ONLY THE FRONT PAGE OF THE |
| REPORT IS SEALED, NOT ALL PAGES. FL ADMIN CODE |
| 61G16.003(1) ARCHITECTS.PLANS, SPECIFICATIONS, REPORTS |
| OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL |
| AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| |
| 1ST ROUND OF COMMENTS. SHEET A-3. PLEASE PROVIDE |
| COMPLIANCE WITH FBC-B WIND DESIGN. THE PLANS REFERENCE |
| THE RESIDENTIAL CODE, R703.13, R616.4, TABLE R301.2(2) |
| & R301.2(2). |
| |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 5-6) COMPLIED. |
| |
| 7) PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 8) PROVISO/ DEFERRED SUBMITTAL: IDENTIFY GLAZING/ |
| MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| 9) PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 10) COMPLIED. THRESHOLDS ACCESS. CODE 404.2.5 |
| |
| 11) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |