2017-08-28 11:22:14 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE MASTER PERMIT APPLICATION INDICATES A DEMO |
| PERMIT FOR FUTURE RENOVATION THE PLUMBING SUB PERMIT IS |
| FOR A RENOVATION PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 2. SHT. C-1 THE SCOPE OF WORK STATES DIVIDE BUILDING |
| INTO 4 OFFICE SPACES BUT THE PLAN ONLY SHOWS 1 BAR |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHT. C-1 THE PROJECT-DATA SHOWS EXISTING BUILDING |
| AREA AS 2364 SF THE SCOPE OF WORK SHOWS EXISTING |
| BUILDING AS 2114 SF AND THE OCCUPANT LOAD SHOWS A TOTAL |
| OF 1972 SF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. SHT. C-3 THE OCCUPANT LOAD IS STATED AT 102 PEOPLE |
| THE PLUMBING FIXTURE REQUIRED SHOWS OCCUPANT LOAD AT 36 |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. WITH A OCCUPANT LOAD OF 102 THE PLUMBING FIXTURE |
| REQUIRED ARE 2 WC AND 2 LAVATORY'S FOR WOMEN AND THE |
| SAME FOR MEN. PER FBC PL TABLE 403.1 |
| |
| 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES |
| SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS |
| TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN |
| AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND |
| NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR |
| SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE |
| WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN |
| 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND |
| THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE |
| FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER |
| FBC PL 405.3.5 |
| |
| 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S. |
| PER FBC ACC 606.2 |
| |
| 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES (380 MM) MINIMUM AND 48 INCHES-MAXIMUM ABOVE THE |
| FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| PER FBC ACC 604.7 DISPENSERS. |
| |
| 9. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| MEASURED TO THE TOP OF THE SEAT. PER FBC ACC 604.4 |
| |
| 10. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL |
| AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER |
| FBC ACC 604.5.1 |
| |
| 11. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 |
| |
| 12. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO |
| THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| |
| 13. TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE, |
| SHALL COMPLY WITH 404 EXCEPT THAT IF THE APPROACH IS TO |
| THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE |
| BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY |
| OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM. DOORS |
| SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE |
| WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. WHERE |
| LOCATED IN THE FRONT PARTITION, THE DOOR OPENING SHALL |
| BE 4 INCHES (100 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED |
| IN THE SIDE WALL OR PARTITION, THE DOOR OPENING SHALL |
| BE 4 INCHES (100 MM) MAXIMUM FROM THE FRONT PARTITION. |
| THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING |
| WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR |
| NEAR THE LATCH. TOILET COMPARTMENT DOORS SHALL NOT |
| SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. PER |
| FBC ACC 604.8.1.2 |
| |
| 14. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 |
| |
| 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE |
| IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT |
| LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1 |
| |
| 18. PLEASE PROVIDE HOT AND COLD WATER RISER DIAGRAM. |
| PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 19. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 20. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PLEASE |
| SHOW NOT ON PLAN. PER WPB AMEND TO FBC 107.2.1 |
| |
| 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY |
| WATER METER. PER WPB UTILITIES |
| |
| 22. PLEASE SHOW CONDENSATE DRAINS FOR AC AND COOLER. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 23. SHT. C-1 THE SCOPE OF WORK UNDER PLUMBING CALLS OUT |
| A WATER FOUNTAIN NONE IS SHOWN ON PLAN PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |