Plan Review Notes
Plan Review Notes For Permit 17080793
Permit Number 17080793
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-28 11:22:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MASTER PERMIT APPLICATION INDICATES A DEMO
 PERMIT FOR FUTURE RENOVATION THE PLUMBING SUB PERMIT IS
 FOR A RENOVATION PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. C-1 THE SCOPE OF WORK STATES DIVIDE BUILDING
 INTO 4 OFFICE SPACES BUT THE PLAN ONLY SHOWS 1 BAR
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. C-1 THE PROJECT-DATA SHOWS EXISTING BUILDING
 AREA AS 2364 SF THE SCOPE OF WORK SHOWS EXISTING
 BUILDING AS 2114 SF AND THE OCCUPANT LOAD SHOWS A TOTAL
 OF 1972 SF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. C-3 THE OCCUPANT LOAD IS STATED AT 102 PEOPLE
 THE PLUMBING FIXTURE REQUIRED SHOWS OCCUPANT LOAD AT 36
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. WITH A OCCUPANT LOAD OF 102 THE PLUMBING FIXTURE
 REQUIRED ARE 2 WC AND 2 LAVATORY'S FOR WOMEN AND THE
 SAME FOR MEN. PER FBC PL TABLE 403.1
  
 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES
 SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS
 TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE
 WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN
 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND
 THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER
 FBC PL 405.3.5
  
 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S.
 PER FBC ACC 606.2
  
 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES (380 MM) MINIMUM AND 48 INCHES-MAXIMUM ABOVE THE
 FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
 PER FBC ACC 604.7 DISPENSERS.
  
 9. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. PER FBC ACC 604.4
  
 10. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 11. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 12. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 13. TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404 EXCEPT THAT IF THE APPROACH IS TO
 THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM. DOORS
 SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE
 WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. WHERE
 LOCATED IN THE FRONT PARTITION, THE DOOR OPENING SHALL
 BE 4 INCHES (100 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED
 IN THE SIDE WALL OR PARTITION, THE DOOR OPENING SHALL
 BE 4 INCHES (100 MM) MAXIMUM FROM THE FRONT PARTITION.
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. PER
 FBC ACC 604.8.1.2
  
 14. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE
 IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT
 LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 18. PLEASE PROVIDE HOT AND COLD WATER RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 19. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 20. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PLEASE
 SHOW NOT ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY
 WATER METER. PER WPB UTILITIES
  
 22. PLEASE SHOW CONDENSATE DRAINS FOR AC AND COOLER.
 PER WPB AMEND TO FBC 107.2.1
  
 23. SHT. C-1 THE SCOPE OF WORK UNDER PLUMBING CALLS OUT
 A WATER FOUNTAIN NONE IS SHOWN ON PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  