2017-08-18 11:23:24329B CLEMATIS STREET
 PERMIT #17080793
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **NOTE: CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY**
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 CALCULATED OCCUPANT LOAD DOES NOT FACTOR ANY STANDING
 ROOM OR CLOSELY SPACED BAR SEATING.
  
 BAR/ASSEMBLY SPACE OCCPUANT LOAD EXCEEDS 100 PERSONS
 AND NO FIRE SPRINKLER PROTECTION PROVIDED PER FBC
 903.2.1.2.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 NO DOOR/HARDWARD SCHEDULE PROVIDED. FOR ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 THE BACK SEATING AREA DOOR LEADING TO THE REAR
 (SECONDARY) EXIT HAS A SWING THAT IS AGAINST THE FLOW
 OF EGRESS FOR MORE THAN 50 PERSONS.
  
 INSUFFICIENT EMERGENCY LIGHTING PROVIDED IN MAIN
 ASSEMBLY AREA. EMERGENCY ILLUMINATION SHALL BE PROVIDED
 FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF
 NORMAL LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  
  