2017-08-23 14:08:30 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SHEET E-1 HAS SEVERAL NOTES (THE NOTES THAT ARE NOT |
| NUMBERED) THAT APPLY TO RESIDENTIAL INSTALLATIONS. |
| EXAMPLE: 75% OF LAMPS SHALL BE HIGH EFFICIENCY, |
| RECEPTACLES TO BE TAMPER RESISTANT, AFCI PROTECTION, |
| ETC. REMOVE ALL NOTES NOT APPLICABLE TO PROJECT. FBC |
| 107.2.1 |
| 2. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62 |
| 3. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW |
| LIGHTING. FBC CE 405.2.4 |
| 4. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 |
| 5. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 |
| 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. NO AUTOMATIC CONTROL IS |
| CURRENTLY SHOWN. FBC CE 405.2.2, 405.2.2.2 |
| 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR SYSTEMS TO INCLUDE BUT NOT BE LIMITED TO |
| FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| WALK IN COOLER, ETC. FBC 105.1 |
| 8. CIRCUIT 16,18 IS DESIGNATED IN PANEL SCHEDULE FOR |
| WALK IN COOLER, BUT CIRCUIT 18 IS SHOWN FEEDING SEVERAL |
| RECEPTACLES. CORRECT DISCREPANCY. FBC 107.2.1, NEC |
| 215.5, 408.4 |
| 9. PROVIDE REQUIRED GFCI SERVICE OUTLET FOR A/C |
| EQUIPMENT. NEC 210.63 |
| 10. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| CORRECTION. NEC 700.12(F) |
| 11. PANEL SCHEDULE SHOWS AHU-1, AHU-2, CU-1, AND CU-2. |
| ELECTRICAL PLAN SHOWS RTU-1 ONLY. PROVIDE CORRECTION, |
| UPDATE PANEL LOAD IF NECESSARY. FBC 107.2.1; NEC 220, |
| 408.4 |
| 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 13. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9 |
| 14. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| AVAILABLE PER NEC 110.24. |
| 15. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| USING METHOD FOR COMMERCIAL SERVICE. CURRENT LOAD |
| STATED FOR RECEPTACLES IS NOT ACCURATE. NEC 220; FBC |
| 107.2.1 |
| 16. NOTE UNDER PANEL SCHEDULE STATES THAT ALL 15 AN 20 |
| AMP BREAKERS SHOULD BE AFCI TYPE. CLARIFY AND/OR |
| CORRECT. FBC 107.2.1; NEC 210.12 |
| 17. NOTE ON SHEET E-2 STATES THAT "SMOKE DETECTORS TO |
| BE HARD WIRED WITH BATTERY BACK UP". NO SMOKE DETECTORS |
| SHOWN ON PLAN. A SEPARATE PERMIT IS REQUIRED FOR FIRE |
| ALARM INSTALLATIONS. PLEASE CLARIFY AND/OR CORRECT. FBC |
| 105.1, 107.2.1 |
| 18. SCOPE OF WORK ON C-1 STATES THAT THERE WILL BE 4 |
| NEW SERVICES WITH 4 NEW PANELS. THIS WORK IS NOT |
| REFLECTED ON PLAN. PLEASE CLARIFY AND/OR CORRECT. FBC |
| 107.2.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |