2017-08-23 14:08:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-1 HAS SEVERAL NOTES (THE NOTES THAT ARE NOT
 NUMBERED) THAT APPLY TO RESIDENTIAL INSTALLATIONS.
 EXAMPLE: 75% OF LAMPS SHALL BE HIGH EFFICIENCY,
 RECEPTACLES TO BE TAMPER RESISTANT, AFCI PROTECTION,
 ETC. REMOVE ALL NOTES NOT APPLICABLE TO PROJECT. FBC
 107.2.1
 2. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62
 3. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. FBC CE 405.2.4
 4. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1
 5. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. NO AUTOMATIC CONTROL IS
 CURRENTLY SHOWN. FBC CE 405.2.2, 405.2.2.2
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR SYSTEMS TO INCLUDE BUT NOT BE LIMITED TO
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK IN COOLER, ETC. FBC 105.1
 8. CIRCUIT 16,18 IS DESIGNATED IN PANEL SCHEDULE FOR
 WALK IN COOLER, BUT CIRCUIT 18 IS SHOWN FEEDING SEVERAL
 RECEPTACLES. CORRECT DISCREPANCY. FBC 107.2.1, NEC
 215.5, 408.4
 9. PROVIDE REQUIRED GFCI SERVICE OUTLET FOR A/C
 EQUIPMENT. NEC 210.63
 10. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 11. PANEL SCHEDULE SHOWS AHU-1, AHU-2, CU-1, AND CU-2.
 ELECTRICAL PLAN SHOWS RTU-1 ONLY. PROVIDE CORRECTION,
 UPDATE PANEL LOAD IF NECESSARY. FBC 107.2.1; NEC 220,
 408.4
 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 13. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 14. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
 15. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 USING METHOD FOR COMMERCIAL SERVICE. CURRENT LOAD
 STATED FOR RECEPTACLES IS NOT ACCURATE. NEC 220; FBC
 107.2.1
 16. NOTE UNDER PANEL SCHEDULE STATES THAT ALL 15 AN 20
 AMP BREAKERS SHOULD BE AFCI TYPE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 210.12
 17. NOTE ON SHEET E-2 STATES THAT "SMOKE DETECTORS TO
 BE HARD WIRED WITH BATTERY BACK UP". NO SMOKE DETECTORS
 SHOWN ON PLAN. A SEPARATE PERMIT IS REQUIRED FOR FIRE
 ALARM INSTALLATIONS. PLEASE CLARIFY AND/OR CORRECT. FBC
 105.1, 107.2.1
 18. SCOPE OF WORK ON C-1 STATES THAT THERE WILL BE 4
 NEW SERVICES WITH 4 NEW PANELS. THIS WORK IS NOT
 REFLECTED ON PLAN. PLEASE CLARIFY AND/OR CORRECT. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  