2017-08-21 10:20:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080793
 ADD: 329 CLEMATIS ST. SUITE: B
 CONT: DURHAM BROTHERS
 TEL: 561-662-0736
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 21/ 2017
 ACTION: DENIED
  
 1) SITE THE OLD MYERS LUGGAGE STORE. THE COVER SHEET
 INDICATES THIS TENANT SPACE WAS A MERCANTILE AND IS
 PROPOSED TO BE AN A-2 OCCUPANCY. A CHANGE OF OCCUPANCY
 IS MORE STRINGENT THAN A LEVEL II ALTERATION AND MUST
 MEET ALL OF THE REQUIREMENTS FOUND IN THE 2014 FBC-
 EXISTING BUILDING CODE. PLEASE REFER TO CHAPTER 10,
 CHANGE OF OCCUPANCY. 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1A) THE COVERSHEET DOES NOT PROVIDE THE REQUIRED
 OCCUPANCY SEPARATION REQUIREMENT FOUND IN TABLE 508.4
 OF THE 2014 FBC-B. SHEET A-1 DOES INDICATE EXISTING 2
 HR. OCCUPANCY SEPARATION BUT DOES NOT DECLARE THE TYPE
 OF WALL ASSEMBLY TO MAKE UP THE EXISTING 2 HR. FIRE
 BARRIER. FBC-B 707.3.9 SEPARATED OCCUPANCIES & 707.5
 CONTINUITY.
  
 1B) SINCE THE OCCUPANCY SEPARATION WALLS WILL HAVE
 ADDITIONAL ELECTRICAL AND OR PLUMBING PLEASE PROVIDE
 FIRE RATED WALL PENETRATION DETAILS PER FBC-B 707.7.
 PENETRATIONS. PENETRATIONS OF FIRE BARRIERS SHALL
 COMPLY WITH SECTION 714 OF THE FBC-B.
  
 1C) PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-EXISTING BUILDING CODE SECTION 1012.1.2 FIRE
 PROTECTION AND INTERIOR FINISH. THE PROVISIONS OF
 SECTIONS 1012.2 AND 1012.3 FOR FIRE PROTECTION AND
 INTERIOR FINISH, RESPECTIVELY, SHALL APPLY TO ALL
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 1D) PLEASE REVIEW UNDER CHAPTER 10 OF THE EXISTING
 BUILDING CODE THE REQUIREMENT FOR FIRE SPRINKLERS. 2014
 EXT. BLDG. CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 EXST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2014 FBC-B SECTION F] 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR
 MORE.
  
 2) SHEET A-1:
 2A) PLEASE REVIEW THE DOOR SWING FOR THE DOOR BETWEEN
 THE BACK SEATING ROOM AND THE RESTROOM VESTIBULE. THIS
 DOOR SWINGS AGAINST THE MEANS OF EGRESS WITH AN
 OCCUPANT LOAD GREATER THAN 50 OCCUPANTS. PLEASE REVIEW
 SECTION 1008.1.2 OF THE 2014 FBC-B. 1008.1.2 DOOR
 SWING. DOORS SHALL SWING IN THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING A ROOM OR AREA CONTAINING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 2B) THE REAR OF THE TENANT SPACE IS LABELED A OFFICE
 AREA BUT LOOKS MORE LIKE A STORAGE AREA WITH AN EXIT
 ACCESS GOING THROUGH. NOTE THERE IS A SIGNAGE ON PLANS
 NO STORAGE, IF TO BE CONSIDERED AN OFFICE AREA SHOW
 FURNITURE AND IT NOT BLOCKING THE MEANS OF EGRESS.
 2014 FBC-B 014.2 EGRESS THROUGH INTERVENING SPACES.
 (4). EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 2C) SHEET A1 SHOWS 4 ACCESSIBLE SEATS. THE LIFE SAFETY
 SHEET DOES NOT SHOW COMPLIANCE WITH THE :
 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 98 SEATS X 0.05= 4.9 OR 5 SEATS, 4SHOWN ON
 PLANS.
  
 2D) FBC-ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES. THE PLANS
 DO NOT SHOW COMPLIANCE WITH: 902.1 .DINING SURFACES AND
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2E) SHEET A-2 SHOWS THE ACCESS AISLE WITH A HASH LINE
 AT 36 INCHES WIDE. PLEASE REVIEW UNDER AN ASSEMBLY
 OCCUPANCY WITH AN OCCUPANT LOAD OF 102 FBC-B 1028.9
 .1.4. FORTY-TWO INCHES FOR LEVEL OR RAMPED AISLE HAVING
 SEATING ON BOTH SIDES.
  
 3) SHEET A2 SHOWS THE DEMOLITION AND REMOVAL OF THE
 FRONT DISPLAY WINDOWS AND STOREFRONT. SHEET A3 SHOWS
 THE NEW LOCATION OF THE STOREFRONT. PLEASE PROVIDE THE
 LOCATION OF THE FRONT PROPERTY LINE. THE FRONT DOOR IS
 NOT TO SWING BEYOND THE PROPERTY LINE. 2014 FBC-B
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 4)SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH FBC-B WIND
 DESIGN. THE PLANS REFERENCE THE RESIDENTIAL CODE,
 R703.13, R616.4, TABLE R301.2(2) & R301.2(2).
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) SHEET A-3. SHOWS A DETAIL LISTED AS A/3. PLEASE
 REVIEW THIS DETAIL , THE STUD IS DETAILED AS METAL STUD
 20 GAUGE W/ TOP AND BOTTOM STEEL PLATES, STUDS AT 16
 INCHES O. C. THE LEFT SIDE OF THE DETAIL LIST 1X2 INCH
 FURRING AT 24 INCHES ON CENTER, THE RIGHT SIDE OF THE
 DETAIL INDICATES THE INSTALLATION OF 5/8 INCH PLYWOOD
 SHEATHING NAILED WITH 8D RING SHANK NAILS @ 6 INCHES ON
 CENTER, NAILS USE ON METAL STUDS?
 ON THE SAME RIGHT SIDE THE FINISH IS LABELED AS 2 COAT
 STUCCO AND ALSO 5/8 INCH TYPE X GBD. DISCREPANCIES IN
 MATERIALS, SPACING, TO MANY ERRORS TO COMMENT ON.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-3 WALL PRESSURES ARE STATED TO BE ALLOWABLE
 (VASD):
 6A) THE POSITIVE PRESSURES APPEAR TO BE VULT AND NOTE,
 THE SQUARE FOOT AREA IS NOT GIVEN, AND THE SAME
 POSITIVE 58.3 IN BOTH WALL ZONES 4 & 5!!! 2014 FBC-B
 1603.1.4 WIND DESIGN DATA.
  
 6B) THE NEGATIVE PRESSURES APPEAR TO BE VULT AND THE
 SQUARE FEET OF AREA FOR THE PRESSURES IS NOT GIVEN.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER