Plan Review Notes
Plan Review Notes For Permit 17080780
Permit Number 17080780
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-08-30 10:30:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY,
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 4.6.11 CHANGE OF USE OR OCCUPANCY CLASSIFICATION. IN
 ANY BUILDING OR STRUCTURE, WHETHER OR NOT A PHYSICAL
 ALTERATION IS NEEDED, A CHANGE FROM ONE USE OR
 OCCUPANCY CLASSIFICATION TO ANOTHER SHALL COMPLY WITH
 4.6.7.
  
 4.6.7 BUILDING REHABILITATION.
 4.6.7.1 REHABILITATION WORK ON EXISTING BUILDINGS SHALL
 BE CLASSIFIED AS ONE OF THE FOLLOWING WORK CATEGORIES
 IN ACCORDANCE WITH 43.2.2.1:
 (1) REPAIR
 (2) RENOVATION
 (3) MODIFICATION
 (4) RECONSTRUCTION
 (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION
 (6) ADDITION
  
 PLEASE PROVIDE THE PREVIOUS OCCUPANCY AND THE PROPOSED
 NEW ONE PER (5).
  
  
  
 2) WHAT IS THE SCOPE OF THIS DAY-CARE, PLEASE PROVIDE
 THE CLASSIFICATION OF OCCUPANCY
  
 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4.
 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PART-DAY
 PRESCHOOLS, KINDERGARTENS, AND OTHER SCHOOLS WHOSE
 PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH THE
 CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE,
 SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 14.
  
 PLEASE PROVIDE A BRIEF SCOPE OF THE FUNCTION OF THIS
 DAYCARE.
  
  
 3) A FIRE ALARM IS NOT INDICATED ANYWHERE ON THIS PLAN,
 EXISTING OR PROPOSED.
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST
 ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE
 OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE
 WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE WITH SECTION 9.6.
  
 PLEASE PROVIDE AN APPLICABLE NOTE TO INSTALL A FIRE
 ALARM
  
  
 4) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR
 SIZE OR HARDWARE TO THE BATHROOM.
  
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
 PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF
 HARDWARE.
  
  
 5) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR
 SIZES OR EXIT HARDWARE TO THE TWO EXIT DOORS OF THE NEW
 SPACE.
  
 16.2.2.2 DOORS.
 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF
 HARDWARE
  
  
  
  
 6) THERE IS NO EXIT SIGN OVER THE REAR DOOR. THIS DOOR
 IS A REQUIRED EXIT THAT IS REQUIRED TO BE MARKED.
  
 16.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN
 ACCORDANCE WITH BOTH OF THE FOLLOWING CRITERIA:
 (1) THEY SHALL BE PROVIDED ON EVERY STORY.
 (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY
 STORY AND MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL
 BE PERMITTED TO BE COMMON FOR THE DISTANCE PERMITTED AS
 COMMON PATH OF TRAVEL BY 16.2.5.3.
  
 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE PROVIDE EXIT SIGNAGE
  
  
  
 7) THERE ARE NO EMERGENCY LIGHTS INDICATED IN THE
 COMMON AREAS.
  
 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 IN THE
 FOLLOWING AREAS:
 (1) INTERIOR STAIRS AND CORRIDORS
 (2) ASSEMBLY USE SPACES
 (3) FLEXIBLE AND OPEN PLAN BUILDINGS
 (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS
 (5) SHOPS AND LABORATORIES
  
 PLEASE PROVIDE FOR THE REQUIRED EMERGENCY LIGHTING.
  
  
  
 8) THERE IS AN ASSEMBLY SPACE INDICATED NEXT TO THE
 PROPOSED DAYCARE EXPANSION AREA. THERE IS NO FIRE RATED
 SEPARATION INDICATED FOR THIS ESIXTING WALL.
  
 6.1.14.4 SEPARATED OCCUPANCIES.
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE
 COMPLETELY SEPARATED FROM OTHER OCCUPANCIES
 BY FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN
 6.1.14.4.2, 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE
 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING SEPARATIONS.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE RESISTANCE?RATED, 2-HOUR FIRE
 RESISTANCE?RATED, OR 1-HOUR FIRE RESISTANCE?RATED AND
 SHALL MEET THE REQUIREMENTS OF CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE REDUCED BY 1 HOUR, BUT IN NO CASE SHALL
 IT BE REDUCED TO LESS THAN 1 HOUR, WHERE THE BUILDING
 IS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE DOUBLE-DAGGER FOOTNOTE IN THE TABLE.
  
 6.1.14.4.4 OCCUPANCY SEPARATION SHALL BE VERTICAL,
 HORIZONTAL, OR BOTH OR, WHEN NECESSARY, OF SUCH OTHER
 FORM AS REQUIRED TO PROVIDE COMPLETE SEPARATION BETWEEN
 OCCUPANCY DIVISIONS IN THE BUILDING.
  
 PLEASE PROVIDE THE REQUIRED SEPARATION AND WALL
 DETAILS.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  