2017-08-30 10:30:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY, |
| |
| PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES |
| |
| 4.6.11 CHANGE OF USE OR OCCUPANCY CLASSIFICATION. IN |
| ANY BUILDING OR STRUCTURE, WHETHER OR NOT A PHYSICAL |
| ALTERATION IS NEEDED, A CHANGE FROM ONE USE OR |
| OCCUPANCY CLASSIFICATION TO ANOTHER SHALL COMPLY WITH |
| 4.6.7. |
| |
| 4.6.7 BUILDING REHABILITATION. |
| 4.6.7.1 REHABILITATION WORK ON EXISTING BUILDINGS SHALL |
| BE CLASSIFIED AS ONE OF THE FOLLOWING WORK CATEGORIES |
| IN ACCORDANCE WITH 43.2.2.1: |
| (1) REPAIR |
| (2) RENOVATION |
| (3) MODIFICATION |
| (4) RECONSTRUCTION |
| (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION |
| (6) ADDITION |
| |
| PLEASE PROVIDE THE PREVIOUS OCCUPANCY AND THE PROPOSED |
| NEW ONE PER (5). |
| |
| |
| |
| 2) WHAT IS THE SCOPE OF THIS DAY-CARE, PLEASE PROVIDE |
| THE CLASSIFICATION OF OCCUPANCY |
| |
| 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4. |
| 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PART-DAY |
| PRESCHOOLS, KINDERGARTENS, AND OTHER SCHOOLS WHOSE |
| PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH THE |
| CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE, |
| SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 14. |
| |
| PLEASE PROVIDE A BRIEF SCOPE OF THE FUNCTION OF THIS |
| DAYCARE. |
| |
| |
| 3) A FIRE ALARM IS NOT INDICATED ANYWHERE ON THIS PLAN, |
| EXISTING OR PROPOSED. |
| |
| 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN |
| DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST |
| ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE |
| OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE |
| WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM |
| IN ACCORDANCE WITH SECTION 9.6. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE TO INSTALL A FIRE |
| ALARM |
| |
| |
| 4) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR |
| SIZE OR HARDWARE TO THE BATHROOM. |
| |
| 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR |
| FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE |
| READILY ACCESSIBLE TO THE STAFF. |
| |
| PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF |
| HARDWARE. |
| |
| |
| 5) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR |
| SIZES OR EXIT HARDWARE TO THE TWO EXIT DOORS OF THE NEW |
| SPACE. |
| |
| 16.2.2.2 DOORS. |
| 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| OPERATION FROM THE EGRESS SIDE. |
| 7.2.1.5.5 KEY-OPERATED LOCKS. |
| 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, |
| PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| THROUGH 43 FOR THE SPECIFIC OCCUPANCY. |
| (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND |
| THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE |
| DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| BUILDING IS |
| OCCUPIED. |
| (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| DISTINGUISHABLE AS LOCKED. |
| (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| INSIDE THE BUILDING WHEN IT IS LOCKED. |
| |
| PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF |
| HARDWARE |
| |
| |
| |
| |
| 6) THERE IS NO EXIT SIGN OVER THE REAR DOOR. THIS DOOR |
| IS A REQUIRED EXIT THAT IS REQUIRED TO BE MARKED. |
| |
| 16.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN |
| ACCORDANCE WITH BOTH OF THE FOLLOWING CRITERIA: |
| (1) THEY SHALL BE PROVIDED ON EVERY STORY. |
| (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY |
| STORY AND MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL |
| BE PERMITTED TO BE COMMON FOR THE DISTANCE PERMITTED AS |
| COMMON PATH OF TRAVEL BY 16.2.5.3. |
| |
| 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| |
| PLEASE PROVIDE EXIT SIGNAGE |
| |
| |
| |
| 7) THERE ARE NO EMERGENCY LIGHTS INDICATED IN THE |
| COMMON AREAS. |
| |
| 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.9 IN THE |
| FOLLOWING AREAS: |
| (1) INTERIOR STAIRS AND CORRIDORS |
| (2) ASSEMBLY USE SPACES |
| (3) FLEXIBLE AND OPEN PLAN BUILDINGS |
| (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS |
| (5) SHOPS AND LABORATORIES |
| |
| PLEASE PROVIDE FOR THE REQUIRED EMERGENCY LIGHTING. |
| |
| |
| |
| 8) THERE IS AN ASSEMBLY SPACE INDICATED NEXT TO THE |
| PROPOSED DAYCARE EXPANSION AREA. THERE IS NO FIRE RATED |
| SEPARATION INDICATED FOR THIS ESIXTING WALL. |
| |
| 6.1.14.4 SEPARATED OCCUPANCIES. |
| 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| EACH PART OF THE BUILDING COMPRISING A DISTINCT |
| OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE |
| COMPLETELY SEPARATED FROM OTHER OCCUPANCIES |
| BY FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN |
| 6.1.14.4.2, 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE |
| 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY |
| APPROVED EXISTING SEPARATIONS. |
| 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS |
| 3-HOUR FIRE RESISTANCE?RATED, 2-HOUR FIRE |
| RESISTANCE?RATED, OR 1-HOUR FIRE RESISTANCE?RATED AND |
| SHALL MEET THE REQUIREMENTS OF CHAPTER 8. |
| 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| IN TABLE |
| 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| PERMITTED TO BE REDUCED BY 1 HOUR, BUT IN NO CASE SHALL |
| IT BE REDUCED TO LESS THAN 1 HOUR, WHERE THE BUILDING |
| IS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) AND |
| SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| BY THE DOUBLE-DAGGER FOOTNOTE IN THE TABLE. |
| |
| 6.1.14.4.4 OCCUPANCY SEPARATION SHALL BE VERTICAL, |
| HORIZONTAL, OR BOTH OR, WHEN NECESSARY, OF SUCH OTHER |
| FORM AS REQUIRED TO PROVIDE COMPLETE SEPARATION BETWEEN |
| OCCUPANCY DIVISIONS IN THE BUILDING. |
| |
| PLEASE PROVIDE THE REQUIRED SEPARATION AND WALL |
| DETAILS. |
| |
| |
| |
| 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |