2017-09-28 10:18:30 | 1) THE GREASE TRAP CALCULATIONS FROM MESSLER & |
| ASSOCIATES REFER TO AN 80 GALLON GREASE TRAP BUT THE |
| SPECIFICATIONS ARE FOR A 75 GPM UNIT. CLARIFY.IF AN 80 |
| GPM UNIT IS REQUIRED YOU CANNOT INSTALL A 75 GPM UNIT. |
| 2) THE HAND SINK IN THE SERVICE AREA HAS BEEN RELOCATED |
| BUT IT IS NOT SHOWN ON THE DOMESTIC PLUMBING RISER OR |
| KITCHEN WASTE RISER. CLARIFY. |
| 3) THE KITCHEN WASTE RISER SHOWS A VENT WITH NO FIXTURE |
| ON IT THAT IS NOW A FLAT, DRY VENT AND IN VIOLATION OF |
| 2014 FBC-PLUMBING SEC.905.3. |
| 4) A SERVICE SINK, NOT A LAUNDRY SINK IS REQD. PER THE |
| 2014 FBC -PLUMBING TABLE 403.1. |
| 5) A VENT IS REQD. ON THE SERVICE SINK. 2014 FBC - |
| PLUMBING SEC.901.2, 901.2.1. |
| 6) IS THERE A DRAIN ON THE STEAM TABLE TO THE SANITARY |
| SYSTEM? CLARIFY. IF SO, SHOW THE DRAIN AND SIZE OF |
| DRAIN ON THE PLUMBING RISER. WASTE WATER TEMPERATURE |
| DISCHARGED TO THE SANITARY SYSTEM SHALL NOT EXCEED 140 |
| DEGREES. 2014 FBC-PLUMBING SEC.803.1. |
| 7) A CLEAR FLOOR SPACE OF 60 INCHES WIDE MINIMUM |
| MEASURED BY 56 INCHES DEEP MINIMUM SHALL BE PROVIDED |
| FOR THE WATER CLOSET PER 2014 FBC-ACCESS. SEC.604.3.1. |
| NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED |
| WITHIN THE REQUIRED WATER CLOSET CLEARANCE. YOUR |
| DIMENSIONS ON THE PLANS ARE REVERSED. YOU SHOW 60 |
| INCHES DEEP AND 56 INCHES WIDE. REVISE. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED |
| DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE |
| SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT |
| #16041117). SUBMIT A SEPARATE ADDITIONAL REVISION FOR |
| THE NOTED CHANGES TO THE PLUMBING PLAN. REFER TO |
| COMMENTS # 2, 3,4,5,6,7, |
| |
| |