2017-09-28 10:18:301) THE GREASE TRAP CALCULATIONS FROM MESSLER &
 ASSOCIATES REFER TO AN 80 GALLON GREASE TRAP BUT THE
 SPECIFICATIONS ARE FOR A 75 GPM UNIT. CLARIFY.IF AN 80
 GPM UNIT IS REQUIRED YOU CANNOT INSTALL A 75 GPM UNIT.
 2) THE HAND SINK IN THE SERVICE AREA HAS BEEN RELOCATED
 BUT IT IS NOT SHOWN ON THE DOMESTIC PLUMBING RISER OR
 KITCHEN WASTE RISER. CLARIFY.
 3) THE KITCHEN WASTE RISER SHOWS A VENT WITH NO FIXTURE
 ON IT THAT IS NOW A FLAT, DRY VENT AND IN VIOLATION OF
 2014 FBC-PLUMBING SEC.905.3.
 4) A SERVICE SINK, NOT A LAUNDRY SINK IS REQD. PER THE
 2014 FBC -PLUMBING TABLE 403.1.
 5) A VENT IS REQD. ON THE SERVICE SINK. 2014 FBC -
 PLUMBING SEC.901.2, 901.2.1.
 6) IS THERE A DRAIN ON THE STEAM TABLE TO THE SANITARY
 SYSTEM? CLARIFY. IF SO, SHOW THE DRAIN AND SIZE OF
 DRAIN ON THE PLUMBING RISER. WASTE WATER TEMPERATURE
 DISCHARGED TO THE SANITARY SYSTEM SHALL NOT EXCEED 140
 DEGREES. 2014 FBC-PLUMBING SEC.803.1.
 7) A CLEAR FLOOR SPACE OF 60 INCHES WIDE MINIMUM
 MEASURED BY 56 INCHES DEEP MINIMUM SHALL BE PROVIDED
 FOR THE WATER CLOSET PER 2014 FBC-ACCESS. SEC.604.3.1.
 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED
 WITHIN THE REQUIRED WATER CLOSET CLEARANCE. YOUR
 DIMENSIONS ON THE PLANS ARE REVERSED. YOU SHOW 60
 INCHES DEEP AND 56 INCHES WIDE. REVISE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
 NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED
 DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE
 SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT
 #16041117). SUBMIT A SEPARATE ADDITIONAL REVISION FOR
 THE NOTED CHANGES TO THE PLUMBING PLAN. REFER TO
 COMMENTS # 2, 3,4,5,6,7,
  
  