2017-08-21 09:53:19 | 1) GREASE TRAP SIZING DETAILS - THE BOTTOM OF THE |
| SIZING DETAILS FROM THE GREASE MONKEY SIZING SUMMARY |
| PAGE HAVE BEEN CUT OFF. SUBMIT THE SIZING DETAILS THAT |
| SHOW ALL CRITERIA/CALCULATIONS. WPB AMEND. TO FBC SEC. |
| 107.2.1, 2014 FBC-PLUMBING SEC. 1003.2. |
| 2) SHT. 3 OF 3 - THE KITCHEN WASTE RISER STILL SHOWS AN |
| EXISTING GREASE INTERCEPTOR. SUBMIT A REVISED KITCHEN |
| WASTE RISER DIAGRAM SHOWING THE GB GREASE TRAP..WPB |
| AMEND. TP FBC SEC. 107.3.5.1.3. |
| 3) SHT. 2 OF 3 OF THE REVISED PLANS SHOWS A MOP SINK IN |
| THE STORAGE ROOM NEXT TO THE RESTROOM WHICH WAS NOT ON |
| THE ORIGINAL PLANS. SUBMIT A REVISED SANITARY AND WATER |
| RISER DIAGRAM THAT SHOWS THE MOP SINK. WPB AMEND TO FBC |
| SEC. 107.2.1. |
| 4) THE SINK THAT HAS BEEN RELOCATED FROM THE KITCHEN |
| AREA TO NEAR THE JUICE BAR SHALL BE VENTED ON THE |
| PLUMBING RISER. 2014 FBC-PLUMBING SEC.901.2.1. |
| 5) SHT. 3 OF 3 - SHOW THE WIDTH AND LENGTH OF THE |
| TOILET ROOM. THE PLANS SHOW THE LAVATORY IN THE TOILET |
| ROOM RELOCATED ADJACENT TO THE WATER CLOSET. A CLEAR |
| FLOOR SPACE 60 INCHES WIDE MINIMUM BY 56 INCHES DEEP |
| MINIMUM SHALL BE PROVIDED FOR THE WATER CLOSET. NO |
| OTHER FIXTURES OR OBSTRUCTION SHALL BE LOCATED WITHIN |
| THE REQUIRED WATER CLOSET CLEARANCE PER THE 2014 |
| FBC-ACCESS. SEC.604.3.2. |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GREASE |
| TRAP TO BE INSTALLED. 2014 FBC-PLUMBING SEC. 1003.2. |
| |
| NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED |
| DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE |
| SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT |
| #16041117). SUBMIT A SEPARATE REVISION FOR THE NOTED |
| CHANGES. |
| |