Plan Review Notes
Plan Review Notes For Permit 17080713
Permit Number 17080713
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-21 09:53:191) GREASE TRAP SIZING DETAILS - THE BOTTOM OF THE
 SIZING DETAILS FROM THE GREASE MONKEY SIZING SUMMARY
 PAGE HAVE BEEN CUT OFF. SUBMIT THE SIZING DETAILS THAT
 SHOW ALL CRITERIA/CALCULATIONS. WPB AMEND. TO FBC SEC.
 107.2.1, 2014 FBC-PLUMBING SEC. 1003.2.
 2) SHT. 3 OF 3 - THE KITCHEN WASTE RISER STILL SHOWS AN
 EXISTING GREASE INTERCEPTOR. SUBMIT A REVISED KITCHEN
 WASTE RISER DIAGRAM SHOWING THE GB GREASE TRAP..WPB
 AMEND. TP FBC SEC. 107.3.5.1.3.
 3) SHT. 2 OF 3 OF THE REVISED PLANS SHOWS A MOP SINK IN
 THE STORAGE ROOM NEXT TO THE RESTROOM WHICH WAS NOT ON
 THE ORIGINAL PLANS. SUBMIT A REVISED SANITARY AND WATER
 RISER DIAGRAM THAT SHOWS THE MOP SINK. WPB AMEND TO FBC
 SEC. 107.2.1.
 4) THE SINK THAT HAS BEEN RELOCATED FROM THE KITCHEN
 AREA TO NEAR THE JUICE BAR SHALL BE VENTED ON THE
 PLUMBING RISER. 2014 FBC-PLUMBING SEC.901.2.1.
 5) SHT. 3 OF 3 - SHOW THE WIDTH AND LENGTH OF THE
 TOILET ROOM. THE PLANS SHOW THE LAVATORY IN THE TOILET
 ROOM RELOCATED ADJACENT TO THE WATER CLOSET. A CLEAR
 FLOOR SPACE 60 INCHES WIDE MINIMUM BY 56 INCHES DEEP
 MINIMUM SHALL BE PROVIDED FOR THE WATER CLOSET. NO
 OTHER FIXTURES OR OBSTRUCTION SHALL BE LOCATED WITHIN
 THE REQUIRED WATER CLOSET CLEARANCE PER THE 2014
 FBC-ACCESS. SEC.604.3.2.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GREASE
 TRAP TO BE INSTALLED. 2014 FBC-PLUMBING SEC. 1003.2.
  
 NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED
 DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE
 SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT
 #16041117). SUBMIT A SEPARATE REVISION FOR THE NOTED
 CHANGES.
  