2017-11-29 06:01:111) AN AIR ADMITTANCE VALVE CANNOT BE USED TO VENT THE
 ADDED BATHROOM GROUP. THE VENT SYSTEM SERVING EACH
 BUILDING DRAIN SHALL HAVE AT LEAST ONE VENT PIPE THAT
 EXTENDS TO THE OUTDOORS. FBCR SEC.P3102.1.
 2) SHT. A3 NOTES THAT ALL PLUMBING LINES SHALL SLOPE A
 MINIMUM OF 1/8 INCH PER FOOT. PIPING 2 1/2 INCHES OR
 LESS SHALL BE SLOPED A MINIMUM OF 1/4 INCH PER FOOT PER
 FBCR SEC.P3005.4.2.
 3) THE WATER SUPPLY VALVES FOR THE STACKABLE WASHER AND
 DDRYER SHALL BE ACCESSIBLE. FBCR SEC.P2903.9.3.
 4) THE SANITARY RISER SUPPLIED BY THE PLUMBING
 CONTRACTOR NOTES CORE DRILLING THROUGH THE FOOTER. SHOW
 THE SIZE OF THE DRILLED OPENING. TWO COPIES OF A SIGNED
 AND SEALED LETTER FROM THE ARCHITECT OF RECORD SHALL BE
 SUBMITTED VERIFYING THAT THE CORE DRILLING OF THE
 FOOTING WILL NOT COMPROMISE THE STRUCTURAL INTEGRITY OF
 THE FOOTING FOR HANDLING ALL IMPOSED LOADS.FBCR SEC.
 R301, FBCR SEC. R403.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW