2017-08-23 17:25:41BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080681
 W. P. B. PERMIT: 16090560
 ADD: 600 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-267-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 23/2017
 ACTION: BUILDING PROVISO
  
 1) THE M1.0 SHEET NOTE FOR A/C CONDENSER STAND NOTE
 INDICATES FOR REFERENCE ONLY. THE STRUCTURAL
 ATTACHMENTS TO THE ROOF AND THE CONDENSING UNIT STAND
 TO BE VERIFIED BY A STRUCTURAL AND OR SPECIALTY
 ENGINEER.
  
 2) PART OF THE PROVISO AT PERMIT ISSUANCE WAS DEFERRED
 SUBMITTALS LISTED IN THAT GROUP IS PRE-ENGINEERED A/C
 STANDS. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER