2018-10-31 16:01:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012
 5TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW:
 GAS PIPING COMMENTS: DENIED
  
 1. RE: WPB FBC 107.2.1; MANUFACTURER?S SPECIFICATION
 SHEETS REQUIRED SUBMITTALS
 A) NG LINE REGULATOR (MP)
 ? PROVIDE ONE SPEC SHEET TO ACCOMPANY EACH APPLIANCE
 INCLUSIVE OF EXISTING POOL HEATER, NOTING INDOOR OR
 OUTDOOR APPLICATION AND SPECIFY CORRECT VENT LIMITING
 DEVICE OR VENT PROTECTOR AS REQUIRED BY APPLICATION.
 B) TANKLESS WATER HEATER
 ? RINNAI RL75E IS NOT FOR INDOOR INSTALLATION
 1) SUBMIT A UNIT FOR INDOOR USE
 2) PROVIDE DETAIL AND MANUFACTURER?S RECOMMENDED VENT
 TERMINATION KIT SPEC
 3) IDENTIFY RUSKIN LOUVER AS 12 X 18 COMBUSTION AIR
 VENT
 4) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 C) BBQ GRILL
 ? SALES BROCHURE IS NOT ADEQUATE
 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT.
 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 D) EXISTING EQUIPMENT
 ? POOL HEATER
 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT.
 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 2. REVISE THE GAS PIPING RISER DIAGRAM THAT SHOWS THE
 TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE INCLUSIVE OF THE EXISTING POOL HEATER, THE
 RUN FROM THE NEW APPLIANCES BACK TO THE INTERSECTION
 WITH THE BRANCH TO THE EXISTING POOL HEATER, THE RUN
 FROM THAT INTERSECTION TO THE UPGRADED REGULATOR AND
 METER AND THE DISTANCE OF THE LONGEST LENGTH OF PIPING
 FROM THE POINT OF DELIVERY TO THE MOST REMOTE OUTLET
 INCLUSIVE OF THE EXISTING POOL HEATER AND THE LOAD OF
 THE SECTION.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 ADDITIONAL NOTES; DOES NOT APPLY TO PERMIT APPLICATION
  
 1. CITY RECORDS SHOW .5LB GAS ON EXISTING SYSTEM.
 PROVIDE AFFIDAVIT OF GAS PIPING TEST TO INCLUDE OF
 EXISTING SYSTEM FOR FINAL INSPECTION IN ACCORDANCE WITH
 FBC FG 406 TO INSURE IT IS 2PSI CAPABLE.
 2. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715