2018-10-31 16:01:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012 |
| 5TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 3RD REVIEW: |
| GAS PIPING COMMENTS: DENIED |
| |
| 1. RE: WPB FBC 107.2.1; MANUFACTURER?S SPECIFICATION |
| SHEETS REQUIRED SUBMITTALS |
| A) NG LINE REGULATOR (MP) |
| ? PROVIDE ONE SPEC SHEET TO ACCOMPANY EACH APPLIANCE |
| INCLUSIVE OF EXISTING POOL HEATER, NOTING INDOOR OR |
| OUTDOOR APPLICATION AND SPECIFY CORRECT VENT LIMITING |
| DEVICE OR VENT PROTECTOR AS REQUIRED BY APPLICATION. |
| B) TANKLESS WATER HEATER |
| ? RINNAI RL75E IS NOT FOR INDOOR INSTALLATION |
| 1) SUBMIT A UNIT FOR INDOOR USE |
| 2) PROVIDE DETAIL AND MANUFACTURER?S RECOMMENDED VENT |
| TERMINATION KIT SPEC |
| 3) IDENTIFY RUSKIN LOUVER AS 12 X 18 COMBUSTION AIR |
| VENT |
| 4) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| APPLICATION |
| C) BBQ GRILL |
| ? SALES BROCHURE IS NOT ADEQUATE |
| 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT. |
| 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| APPLICATION |
| D) EXISTING EQUIPMENT |
| ? POOL HEATER |
| 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT. |
| 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY |
| APPLICATION |
| 2. REVISE THE GAS PIPING RISER DIAGRAM THAT SHOWS THE |
| TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE INCLUSIVE OF THE EXISTING POOL HEATER, THE |
| RUN FROM THE NEW APPLIANCES BACK TO THE INTERSECTION |
| WITH THE BRANCH TO THE EXISTING POOL HEATER, THE RUN |
| FROM THAT INTERSECTION TO THE UPGRADED REGULATOR AND |
| METER AND THE DISTANCE OF THE LONGEST LENGTH OF PIPING |
| FROM THE POINT OF DELIVERY TO THE MOST REMOTE OUTLET |
| INCLUSIVE OF THE EXISTING POOL HEATER AND THE LOAD OF |
| THE SECTION. |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| ADDITIONAL NOTES; DOES NOT APPLY TO PERMIT APPLICATION |
| |
| 1. CITY RECORDS SHOW .5LB GAS ON EXISTING SYSTEM. |
| PROVIDE AFFIDAVIT OF GAS PIPING TEST TO INCLUDE OF |
| EXISTING SYSTEM FOR FINAL INSPECTION IN ACCORDANCE WITH |
| FBC FG 406 TO INSURE IT IS 2PSI CAPABLE. |
| 2. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES / |
| EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| FGC SEC.305.1, FBC-RES. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |