2018-02-15 09:08:322ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS ARE NOT COMPLIED WITH
 IN ORDER TO EXPEDITE THE APPROVAL OF THIS PLAN I
 SUGGEST A MEETING BE SCHEDULED TO GO OVER COMMENTS
 BEFORE THE NEXT RESUBMITTAL.
  
 CITY RECORDS SHOW MUILT PERMITS ISSUED FOR .5LB GAS ON
 MAIN HOME.
  
 PARTIALLY COMPLIED 1) LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2413. SHOW BTU LOAD ON THE GAS RISER.
  
 2ND REQUEST 2) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
  
 2ND REQUEST 5) THE PLANS INDICATE AN EXISTING GAS
 METER. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 THE GAS OR PLUMBING CONTRACTOR CANNOT TIE INTO THE GAS
 UTILITIES LINE ONLY THE GAS UTILITIES COMPANY CAN DO
 THAT WHICH IS FLORIDA PUBLIC UTILITIES. IF YOU HAVE FPU
 INSTALL A NEW METER WITH A 2PSI REGULATOR SHOW IT ON
 THE RISER ALONG WITH THE DISTANCE FROM THE METER TO THE
 FURTHEST APPLIANCE SHOWN ON THE RISER.
 REMOVE NOTE #4 FROM SCOPE OF WORK.
  
 2ND REQUEST 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 2ND REQUEST 7) SHOW THE DISTANCE FROM THE 2 PSI
 REGULATOR TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL
 GAS TABLE 402.4 (28) FOR THE PROPER PIPE SIZE AND BTU
 LOAD.
  
 NEW COMMENTS:
  
 1. SHOW ON THE GAS RISER THE TRANSITION FROM PE PIPE TO
 TYPE OF PIPING BEFORE INTERRING BUILDING FOR THE
 TANKLESS HEATER. PE PIPING CANNOT RUN IN OR UNDER THE
 BUILDING. PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENT FOR WATER HEATER PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU 505.
  
 3. THE 10 X10 OPENING FOR COMBUSTION AIR SHALL COMPLY
 WITH FBC MECH. 401.5 PROVIDE MANUFACTURE SPECS AND
 PRODUCT APPROVAL. PER WPB AMEND TO FBC 107.2.1
  
 4. SHOW TYPE OF PIPE AND PRESSURE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  