2017-08-29 15:24:11 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE # 1 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE4002.14 |
| 2. NOTE # 11 STATES THAT LIGHTING IN CLOTHES CLOSETS |
| SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH DOESN?T EXIST. |
| PROVIDE CORRECTION. NEC 410.16; FBC RE4003.12 |
| 3. SEVERAL ELECTRICAL NOTES REFER TO EXISTING |
| INSTALLATION, BUT THE PERMIT APPLICATION STATES THIS IS |
| A NEW BUILDING. REMOVE ANY NOTES NOT PERTAINING TO THIS |
| JOB. FBC 107.2.1 |
| 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. NEC 250.94; FBC RE3609.3 |
| 5. PROVIDE SPEC SHEET FOR EXISTING METER CAN SHOWING |
| DOUBLE LUG COMPATIBLE. DESCRIBE METHOD OF DOUBLE LUG |
| TAP. FBC 107.2.1, NEC 110.3 |
| 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| 7. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, LOCATION OF MAIN DISCONNECTS AND |
| LABELING FOR THOSE DISCONNECTS, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| INTERIOR PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, |
| RE3609.3; FBC 107.2.1 |
| 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER FOR PANEL A AT THE NEW BUILDING. NEC |
| 225.31, 225.32 |
| 9. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| RE3607.3 |
| 10. ADDRESS PANEL A LOCATION. OVERCURRENT PROTECTION |
| DEVICES ARE NOT PERMITTED IN THE VICINITY OF EASILY |
| IGNITABLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. PROVIDE |
| CLARIFICATION AND/OR CORRECTION. NEC 240.24(D); FBC |
| RE3705.7 |
| 11. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| FBC RE3903.3 |
| 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC CE R404.1 |
| |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |